| 2017-09-19 14:16:41 | DENIED AS FOLLOW; |
| | |
| | 1. SPECIFICATION FOR PLUMBING CODE COMPLIANCE SAY 2010 |
| | FPC ON PAGE P-0.0.00 BUT ON PAGE A-0.0.00 IT REFERS TO |
| | FBC RESIDENTIAL 2014. PLEASE REFLECT AND MAKE |
| | CORRECTION. UNDER GENERAL NOTES P-0.0.00 IT REFERS TO |
| | COMMERCIAL WORK COMPLIANCE WHEN THE RESIDENTIAL IS |
| | STATED OTHER PAGES. FBC AMENDMENTS 107.2.1 |
| | 2. LAY OUT ON PLAN NOT TO CODE, PLEASE PROVIDE AN |
| | ISOMETRIC DIAGRAM. SHOWER EXCEEDS LENGTH ON TRAP AND |
| | VENTING. PLEASE IDENTIFY ALL PIPE AND FIXTURES ON |
| | LAYOUT AND ISOMETRIC. DRAIN, WASTE AND VENT PIPE SIZING |
| | AND RISER DIAGRAM OF ALL FIXTURES NEED TO BE LABELED; |
| | FBC P3004, P3005, FBC AMENDMENTS 107.5.3. |
| | 3. BAR SINK OUTSIDE IN THE BACK HAS WATER TO IT BUT NO |
| | DRAIN WASTE AND VENT. P3004, P3005, |
| | 4. SHOW CLEAN OUT ON 3? RISER STACK TO SECOND FLOOR AND |
| | OUTSIDE OF BUILDING, SIZE CORRECTLY, P-3.1.00. FBC |
| | AMENDMENTS P3005.2 |
| | 5. WASHING MACHINE DOWN STAIRS NEED TO BE ON STAND PIPE |
| | AND VENTED, WASHING MACHINE SHOWN UP STAIR, WATER SHOWN |
| | ON PLAN BUT NO DWV, LAUNDRY TRAY SHOW FLOOR TYPE BUT |
| | SPECS SHOW A MUSTEE FREE STANDING TYPE SEE PAGE AND |
| | VENT TO CODE. P-1.4.01. FBC P3004, P3005. |
| | 6. SHOW SHUT OFF VALVE FOR WATER SERVICE COMING IN THE |
| | HOUSE ON ISOMETRIC PAGE P-3.0.00. FBC P290.9.4 |
| | 7. DETAIL FOR ISLAND SINK ON PAGE P-4.0.00 SHOWS CLEAN |
| | OUT BUT NEED TO SHOW AIR ADMITTANCE VALVE WHERE CLEAN |
| | OUT IS TO REFLECT PLUMBING ISOMETRIC. FBC P3114.4 |
| | 8. SHOWS A GAS GRILL OUTSIDE A GAS PERMIT AND |
| | APPLICATION NEEDS TO BE FILED WITH A QUALIFIED LICENSED |
| | CONTRACTOR. FBC AMENDMENTS 105.1 |
| | 9. FAUCET IN MASTER VALVE SHALL HAVE A TEMPERED MIXING |
| | VALVE. IF INTEGRAL PROVIDE SPECIFICATION OR LOCATION |
| | WHERE IT WILL BE PLACED FBC P2724.1 |
| | 10. ANY PIPE GOING THROUGH A FOUNDATION MUST BE SLEEVED |
| | TO PREVENT COMPRESSION OF PIPE THROUGH FOOTER AND MUST |
| | BE SLEEVED TWO PIPE SIZE LARGER. FBC P2603.4 |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |