| 2017-09-14 13:51:57 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE COMPLETED PANEL SCHEDULE. CURRENTLY, PANEL |
| | SCHEDULE DOES NOT SHOW ANY LOADS FOR EACH CIRCUIT, DOES |
| | NOT SHOW WIRE SIZE, AND DOES NOT INDICATE AFCI OR GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12, |
| | 215.5, 408.4; FBC RE3706.2, RE3902; FBC 107.2.1 |
| | 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 3. SERVICE DISCONNECT ON POWER PLAN IS SHOWN AS |
| | NON-FUSED. OVERCURRENT PROTECTION IS REQUIRED AT THIS |
| | LOCATION. PROVIDE CORRECTION. NEC 230.91; FBC RE |
| | 3603.3.3 |
| | 4. NOTE 6 STATES "PROVIDE ARC FAULT RECEPTACLES AS PER |
| | NEC 210.12". CODE REQUIRES THE FOLLOWING: "ALL |
| | 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| | PROTECTION". PROVIDE CORRECTION TO INCLUDE MORE THAN |
| | RECEPTACLES. NEC 210.12; FBC RE3902.12 |
| | 5. DUE TO THE TYPE OF LIGHT FIXTURES NOT CLARIFIED IN |
| | CLOSETS, PROVIDE NOTE THAT LIGHT FIXTURES SHALL COMPLY |
| | WITH NEC 410.16. NEC 410.16; FBC RE4003.12 |
| | 6. DUE TO THE TYPE OF LIGHT FIXTURES NOT CLARIFIED IN |
| | DAMP LOCATIONS, PROVIDE NOTE THAT LIGHT FIXTURES SHALL |
| | COMPLY WITH NEC 410.10. NEC 410.10(D); FBC RE4003.11 |
| | 7. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC CE R404.1 |
| | 8. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 9. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1 |
| | 10. THE COVERED PATIO SHOWS 2 GFCI STANDARD OUTLETS IN |
| | SUMMER KITCHEN. THESE OUTLETS ARE REQUIRED TO BE |
| | WEATHER PROOF. PROVIDE CORRECTION. NEC 406.9; FBC RE |
| | 4002.8 |
| | 11. CODE STATES: "FOR DWELLING UNITS, ATTACHED GARAGES, |
| | AND DETACHED GARAGES WITH ELECTRIC POWER, AT LEAST ONE |
| | WALL SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE |
| | INSTALLED ON THE EXTERIOR SIDE OF OUTDOOR |
| | ENTRANCES/EXITS WITH GRADE LEVEL ACCESS". SOME OF THE |
| | ENTRY/EXITS DO NOT SHOW A SWITCH TO OUTSIDE LIGHTS. |
| | PROVIDE CORRECTION. NEC 210.70(A)(2)(B), FBC RE3903.3 |
| | 12. THE WATER HEATER SPECIFIED ON SHEET P.0.0.00 IS |
| | SHOWN WITH 4500 WATT ELEMENTS. THE PANEL SCHEDULE SHOWS |
| | A 35 AMP BREAKER FOR THIS UNIT, WHICH IS TOO LARGE PER |
| | CODE. BREAKER SHOULD BE SIZED AT 125% OF THE LOAD, |
| | WHICH WOULD BE A 25 AMP BREAKER. PROVIDE CORRECTION. |
| | NEC 422.13; FBC RE3702.10 |
| | 13. CIRCUITS D-6,8 AND D-13,15 SHOW A 30 AMP DISCONNECT |
| | WITH 25 AMP FUSES. THE SPECS ON SHEET M-1 STATE THAT |
| | THE MOCP IS 30 AMPS FOR EACH UNIT. THE AMPACITY OF THE |
| | CONDUCTORS SUPPLYING MULTIMOTOR AND COMBINATION LOAD |
| | EQUIPMENT SHALL NOT BE LESS THAN THE MINIMUM CIRCUIT |
| | AMPACITY MARKED ON THE EQUIPMENT. THE BRANCH CIRCUIT |
| | OVERCURRENT PROTECTION DEVICE RATING SHALL BE THE SIZE |
| | AND TYPE MARKED ON THE EQUIPMENT. PROVIDE CORRECTION. |
| | NEC 440.22(C); FBC RE3702.11 |
| | 14. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. FBC R314.3, R315.1; FBC 107.2.1 |
| | 15. LIGHT FIXTURE OVER MASTER SHOWER IS NOT VP. PROVIDE |
| | CORRECTION. NEC 410.10(D); FBC RE4003.11 |
| | 16. LAUNDRY ROOM ON 2ND FLOOR DOES NOT SHOW ANY OUTLETS |
| | FOR WASHER OR DRYER AND CIRCUITRY IS NOT INCLUDED IN |
| | PANEL SCHEDULE. PROVIDE CORRECTION. FBC 107.2.1 |
| | 17. RECEPTACLES FOR GARAGE DOOR OPENERS, CIRCUITS D-40 |
| | AND D-41, REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. |
| | NEC 210.8; FBC RE3902.2 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |