| Date |
Text |
| 2017-09-19 15:43:06 | DENIED 9/19/17 |
| | |
| | 1. SPECIFICATION FOR PLUMBING CODE COMPLIANCE SAY 2010 |
| | FPC ON PAGE P-0.0.00C BUT ON PAGE A-0.0.00 IT REFERS TO |
| | FBC RESIDENTIAL 2014. PLEASE REFLECT AND MAKE |
| | CORRECTION. UNDER GENERAL NOTES P-0.0.00C IT REFERS TO |
| | COMMERCIAL WORK COMPLIANCE WHEN THE RESIDENTIAL IS |
| | STATED OTHER PAGES. FBC AMENDMENTS 107.2.1 |
| | 2. LAY OUT ON PLAN NOT TO CODE, PLEASE PROVIDE AN |
| | ISOMETRIC DIAGRAM. PLEASE IDENTIFY ALL PIPE AND |
| | FIXTURES ON LAYOUT AND ISOMETRIC. DRAIN, WASTE AND VENT |
| | PIPE SIZING AND RISER DIAGRAM OF ALL FIXTURES NEED TO |
| | BE LABELED; FBC P3004, P3005, FBC AMENDMENTS 107.5.3. |
| | 3. WASHING MACHINE NEEDS TO BE ON STAND PIPE AND |
| | VENTED, LAUNDRY TRAY SHOW FLOOR TYPE BUT SPECS SHOW A |
| | MUSTEE FREE STANDING TYPE SEE PAGE AND VENT TO CODE. |
| | P-1.3.00C. FBC P3004, P3005. |
| | 4. SHOW CLEAN OUT ON 2? RISER STACK TO STAND PIPE FOR |
| | WASHING MACHINE AND REVENT, P-3.1.00. FBC P3005.2.6 |
| | 5. SHOWS A GAS GRILL OUTSIDE A GAS PERMIT AND |
| | APPLICATION NEEDS TO BE FILED WITH A QUALIFIED LICENSED |
| | CONTRACTOR. FBC AMENDMENTS 105.1 |
| | 6. FAUCET IN MASTER VALVE SHALL HAVE A TEMPERED MIXING |
| | VALVE. IF INTEGRAL PROVIDE SPECIFICATION OR LOCATION |
| | WHERE IT WILL BE PLACED FBC P2724.1 |
| | 7. ANY PIPE GOING THROUGH A FOUNDATION MUST BE SLEEVED |
| | TO PREVENT COMPRESSION OF PIPE THROUGH FOOTER AND MUST |
| | BE SLEEVED TWO PIPE SIZE LARGER. P1.3.00C FBC P2603.4 |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | 561-805-6720 |
| | [email protected] |
| | |
| | |