Plan Review Notes
Plan Review Notes For Permit 17090022
Permit Number 17090022
Review Stop P
Sequence Number 2
Notes
Date Text
2017-11-28 13:53:571) THE WATER HEATER IN THE GARAGE SHALL BE PROTECTED
 FROM PHYSICAL DAMAGE. SUBMIT DETAILS AS TO HOW THIS
 WILL BE ACCOMPLISHED.
 2) PROVIDE THE SHOWER DIMENSIONS FOR THE SHOWER (L X W)
 IN BATHROOM #4. COMPLY WITH FBCR SEC. P2708.1.
 3) SHT. A - 4.202 - DETAIL #8 SHOWS THE SHOWER TO BE
 PITCHED AT 1% SLOPE. SEC. P2709.1 OF 2014 FBCR REQUIRES
 THE SHOWER TO BE PITCHED 1/4 INCH PER FOOT (2 %) TO THE
 DRAIN.
 4) SHT. P.1.3.00 - NOTE #2 - THE DISCHARGE OF THE T & P
 VALVE ON THE WATER HEATER SHALL DISCHARGE THROUGH AN
 AIR GAP IN THE SAME ROOM AS THE WATER HEATER. 2014 FBCR
 SEC. P2803.6.1.
 5) THE BACK TO BACK BATHTUBS IN BATHROMMS # 2 & #3 ON
 THE 2ND FLOOR ARE NOT VENTED. 2014 FBCR SEC. P3101.2,
 P3101.2.1.
 6) PROVISIONS SHALL BE MADE FOR THERMAL EXXPANSION.2014
 FBCR SEC.P2903.4.
 7) SHOW THE FIXTURE CLEARANCES FOR THE FIXTURES PER
 2014 FBCR SEC.P2705.1.
 8) SHT. P.1.4.00 - NOTE #4 - STATES 3/4 INCH HOT AND
 COLD UP TO THE 2ND FLOOR BUT THE PLAN SHOWS 1/2 INCH
 HOT WATER AND SHT P.3.00 SHOWS 1/2 INCH HOT WATER TO
 THE 2ND FLOOR. CLARIFY. THERE ARE THE SAME
 DISCREPANCIES ON THE PLANS FOR OTHER LOCATIONS TO THE
 SECOND FLOOR. THE WATER RISER SIZES ON THE FLOOR PLAN,
 THE NOTES AND THE WATER ISOMETRIC SHALL CORRELATE. WPB
 AMEND. TO FBC SEC. 107.2.1.ALSO SEE SHT. # P.1.4.0.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  