| Plan Review Notes For Permit 17090022 |
| Permit Number |
17090022 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-11-28 13:53:57 | 1) THE WATER HEATER IN THE GARAGE SHALL BE PROTECTED | | | FROM PHYSICAL DAMAGE. SUBMIT DETAILS AS TO HOW THIS | | | WILL BE ACCOMPLISHED. | | | 2) PROVIDE THE SHOWER DIMENSIONS FOR THE SHOWER (L X W) | | | IN BATHROOM #4. COMPLY WITH FBCR SEC. P2708.1. | | | 3) SHT. A - 4.202 - DETAIL #8 SHOWS THE SHOWER TO BE | | | PITCHED AT 1% SLOPE. SEC. P2709.1 OF 2014 FBCR REQUIRES | | | THE SHOWER TO BE PITCHED 1/4 INCH PER FOOT (2 %) TO THE | | | DRAIN. | | | 4) SHT. P.1.3.00 - NOTE #2 - THE DISCHARGE OF THE T & P | | | VALVE ON THE WATER HEATER SHALL DISCHARGE THROUGH AN | | | AIR GAP IN THE SAME ROOM AS THE WATER HEATER. 2014 FBCR | | | SEC. P2803.6.1. | | | 5) THE BACK TO BACK BATHTUBS IN BATHROMMS # 2 & #3 ON | | | THE 2ND FLOOR ARE NOT VENTED. 2014 FBCR SEC. P3101.2, | | | P3101.2.1. | | | 6) PROVISIONS SHALL BE MADE FOR THERMAL EXXPANSION.2014 | | | FBCR SEC.P2903.4. | | | 7) SHOW THE FIXTURE CLEARANCES FOR THE FIXTURES PER | | | 2014 FBCR SEC.P2705.1. | | | 8) SHT. P.1.4.00 - NOTE #4 - STATES 3/4 INCH HOT AND | | | COLD UP TO THE 2ND FLOOR BUT THE PLAN SHOWS 1/2 INCH | | | HOT WATER AND SHT P.3.00 SHOWS 1/2 INCH HOT WATER TO | | | THE 2ND FLOOR. CLARIFY. THERE ARE THE SAME | | | DISCREPANCIES ON THE PLANS FOR OTHER LOCATIONS TO THE | | | SECOND FLOOR. THE WATER RISER SIZES ON THE FLOOR PLAN, | | | THE NOTES AND THE WATER ISOMETRIC SHALL CORRELATE. WPB | | | AMEND. TO FBC SEC. 107.2.1.ALSO SEE SHT. # P.1.4.0.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|