| 2017-11-27 11:24:54 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS |
| | BELOW. |
| | |
| | PREVIOUS COMMENTS CORRECTED ARE NOTED AS CORRECTED. |
| | REMAINING ITEMS HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. |
| | |
| | 1. PROVIDE COMPLETED PANEL SCHEDULE. CURRENTLY, PANEL |
| | SCHEDULE DOES NOT SHOW ANY LOADS FOR EACH CIRCUIT, DOES |
| | NOT SHOW WIRE SIZE, AND DOES NOT INDICATE AFCI OR GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12, |
| | 215.5, 408.4; FBC RE3706.2, RE3902; FBC 107.2.1 |
| | (CURRENTLY, THE PANEL IS SHOWN AS OVERLOADED BECAUSE |
| | THE DEMAND FACTORS ARE NOT APPLIED. ANY LOAD THAT IS |
| | FIGURED IN THE GENERAL LIGHTING LOAD DOES NOT NEED TO |
| | BE LISTED IN THE SCHEDULE. AN ASTERISK IS ACCEPTABLE |
| | THAT EXPLAINS THE LOAD IS INCLUDED IN GENERAL LIGHTING |
| | LOAD.) |
| | 2. CORRECTED. |
| | 3. SERVICE DISCONNECT ON POWER PLAN IS SHOWN AS |
| | NON-FUSED. OVERCURRENT PROTECTION IS REQUIRED AT THIS |
| | LOCATION. PROVIDE CORRECTION. NEC 230.91; FBC RE |
| | 3603.3.3 (THE CURRENT LOAD CALCULATION IS CALLING FOR A |
| | 250 AMP PANEL, BUT THE CORRECTION SUPPLIED SHOWS 200 |
| | AMP FUSES IN A 200 AMP DISCONNECT, WHICH WOULD BE TOO |
| | SMALL FOR THE LOAD. ALTHOUGH, THIS MAY CHANGE DEPENDING |
| | ON THE ACTUAL WATER HEATER LOAD, SEE COMMENT BELOW FOR |
| | WATER HEATER. IF AFTER CORRECTIONS, THE 200 AMP IS |
| | ENOUGH TO HANDLE THE LOAD, THEN NO CORRECTION IS |
| | REQUIRED.) |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. THE WATER HEATER SPECIFIED ON SHEET P.0.0.00 IS |
| | SHOWN WITH 4500 WATT ELEMENTS. THE PANEL SCHEDULE SHOWS |
| | A 35 AMP BREAKER FOR THIS UNIT, WHICH IS TOO LARGE PER |
| | CODE. BREAKER SHOULD BE SIZED AT 125% OF THE LOAD, |
| | WHICH WOULD BE A 25 AMP BREAKER. PROVIDE CORRECTION. |
| | NEC 422.13; FBC RE3702.10 (THE CORRECTION SUPPLIED IS |
| | THE CORRECT BREAKER SIZE FOR 4500 WATT ELEMENTS, BUT |
| | NOW THE PLUMBING SHEET SHOWS A DIFFERENT AMOUNT FOR THE |
| | WATER HEATER, WHICH ALSO DOESN'T AGREE WITH THE AMOUNT |
| | IN THE LOAD CALCULATION. I SEE FROM THE SPECS THAT THIS |
| | WATER HEATER CAN BE WIRED FOR SIMULTANEOUS OR |
| | NON-SIMULTANEOUS OPERATION. FURTHER CLARIFICATION IS |
| | NEEDED TO DETERMINE THE PROPER WIRING AND OCP REQUIRED, |
| | WHICH ALSO MAY CHANGE THE TOTAL LOAD CALCULATION. FEEL |
| | FREE TO CALL OR EMAIL ME AND DISCUSS IF DESIRED.) |
| | 13. CORRECTED. |
| | 14. CORRECTED. |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |