2017-11-30 17:25:41PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: A RECORDED PLAT, A PROPERTY CONTROL NUMBER AND A
 STREET ADDRESS WILL BE REQUIRED BEFORE A BUILDING
 PERMIT WILL BE ISSUED.
  
 1) (PREVIOUS COMMENT) FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES.
 PROVIDE PRODUCT APPROVALS FOR THE SELF-ADHERED ROOFING
 MATERIAL, AND THE BAHAMA SHUTTERS.
  
 2) (PREVIOUS COMMENT) SPECIFY THE METHOD OF ATTACHMENT
 THAT WILL BE USED TO INSTALL THE CONCRETE ROOF TILE. IF
 AN ADHESIVE WILL BE USED, SUBMIT TWO SETS OF THE
 PRODUCT APPROVALS FOR IT. FBC-R905.3.7 & FBC 107.3.4
  
 3) A PRODUCT APPROVAL FOR A METAL ROOF WAS SUBMITTED
 AND THE ROOF NOTES ON SHEET A-1.4.01A AND A-1.4.02A
 REFER TO A METAL ROOF. DO YOU INTEND TO OFFER THE METAL
 ROOF AS AN OPTION TO THE CEMENT TILE ROOF ? IF THAT IS
 THE CASE, PLEASE INDICATE THIS ON THE PLANS. ALSO,
 PROVIDE PRODUCT APPROVALS FOR THE UPPER ROOF VENTS THAT
 CAN BE USED WITH THE METAL ROOF. FBC 107.2.1 AND FBC
 107.3.4
  
 4) (PREVIOUS COMMENT) SHOW COMPLIANCE WITH FBC-R302.12
 DRAFTSTOPPING. IN COMBUSTIBLE CONSTRUCTION WHERE THERE
 IS USABLE SPACE BOTH ABOVE AND BELOW THE CONCEALED
 SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS SHALL BE
 INSTALLED SO THAT THE AREA OF THE CONCEALED SPACE DOES
 NOT EXCEED 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING
 SHALL DIVIDE THE CONCEALED SPACE INTO APPROXIMATELY
 EQUAL AREAS. WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR
 MEMBRANE ABOVE AND A CEILING MEMBRANE BELOW,
 DRAFTSTOPPING SHALL BE PROVIDED IN FLOOR/CEILING
 ASSEMBLIES UNDER THE FOLLOWING CIRCUMSTANCES:
 1. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING.
 2. FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB
 OR PERFORATED MEMBERS.
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  