| 2017-09-25 19:10:12 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P.3.0.01 + P.3.0.00 LABEL ALL FIXTURES ON THE |
| | ISOMETRIC DRAWINGS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. P.3.0.01 + P.3.0.00 SIZE ALL PIPING ON THE |
| | ISOMETRIC DRAWINGS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT. P.3.0.01 THE VENT CONNECTIONS ARE NOT SHOWN ON |
| | THE SANITARY ISOMETRIC DRAWING. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. SHT. P.3.0.01SHOW PTRAPS ON THE SHOWERS AND TUBS ON |
| | THE SANITARY ISOMETRIC DRAWING. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 5. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH |
| | WASTE OR SOIL STACK. PER FBC RES P3005.2.6 |
| | |
| | 6. THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER. PER FBC RES |
| | P3005.2.7 |
| | |
| | 7. SUMMER KITCHEN NOT SHOWN ON SANITARY ISOMETRIC. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. SHT. P4.0.00 DETAIL #1 SHOWS FLOOR DRAIN/ HUBDRAIN |
| | NOT SHOWN ON SANITARY ISOMETRIC PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 9. PLEASE PROVIDE A KEY FOR THE ABBREVIATIONS ON THE |
| | WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL |
| | BATHTUBS SHALL BE LIMITED TO A TEMPERATURE OF NOT |
| | GREATER THAN 120?F (49?C) BY A WATERTEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3. PER FBC RES P2713.3 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |