| 2017-09-19 17:42:55 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | NOTE: A RECORDED PLAT, A PROPERTY CONTROL NUMBER AND A |
| | STREET ADDRESS WILL BE REQUIRED BEFORE A BUILDING |
| | PERMIT WILL BE ISSUED. |
| | |
| | 1) THE BUCK FASTENING REQUIREMENTS ARE NOT PROVIDED IN |
| | THE WINDOW, SLIDING GLASS DOOR AND OUTSWING DOOR |
| | PRODUCT APPROVALS. THE DESIGNER OF RECORD IS REQUIRED |
| | TO SPECIFY THE TYPE OF FASTENER AND SPACING FOR THE |
| | BUCKS ON THE PLANS. FBC-R612 |
| | |
| | 2) ON SHEET S-0.00 UNDER WOOD, IT SHOULD BE NOTED THAT |
| | 8D RINK SHANK NAILS ARE REQUIRED. FBC-R 803.2.3.1 |
| | |
| | 3) THE BEAM IN THE GARAGE ON SHEET S-2.01A HAS AN ID |
| | TAG TS-3, HOWEVER, THERE IS NO TS-3 LISTED IN THE |
| | SCHEDULE ON SHEET S-4.00A. FBC 107.2.1 |
| | |
| | 4) ON SHEET S-2.02A THE TRUSS ANCHORS FOR THE LOWER |
| | ROOF AT THE GARAGE AREA ARE NOT SPECIFIED ON THE PLANS. |
| | FBC 107.2.1 |
| | |
| | 5) ON SHEET S-203 THE TRUSS ANCHOR FOR THE GIRDER TRUSS |
| | AT THE LOWER RIGHT SIDE OF THE DRAWING IS NOT |
| | SPECIFIED. FBC 107.2.1 |
| | |
| | 6) ON SHEET S-203 THERE IS A TYPO AT THE LOWER RIGHT |
| | SIDE OF THE DRAWING THAT SHOWS TWO EXTERIOR WALLS. FBC |
| | 107.2.1 |
| | |
| | 7) SPECIFY THE FASTENERS THAT ARE REQUIRED FOR THE |
| | SIMPSON HU 410 HANGER DETAIL 12/S-3.00 AT THE MASONRY |
| | WALL AND SPECIFY THE CONNECTOR THAT WILL BE USED AT THE |
| | WOOD FRAME WALL. FBC 107.2.1 |
| | |
| | 8) INDICATE THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE WOOD FLOOR TRUSSES TO THE WOOD LEDGERS TO RESIST |
| | LATERAL FORCES ON THE EXTERIOR WALLS. FBC 301.1 |
| | |
| | 9) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES. PROVIDE PRODUCT APPROVALS |
| | FOR THE SELF-ADHERED ROOFING MATERIAL, THE BAHAMA |
| | SHUTTERS AND FOR THE 16' WIDE SECTIONAL GARAGE DOOR ( |
| | THE ONE THAT WAS SUBMITTED IS FOR A MAXIMUM 9' WIDE |
| | GARAGE DOOR). |
| | |
| | 10) SUBMIT A CURRENT PRODUCT APPROVAL FOR THE FIXED |
| | WINDOW. NOA NO. 14-0908.18, EXPIRED PRIOR THE PERMIT |
| | APPLICATION DATE. FBC 107.3.4 |
| | |
| | 11) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO INSTALL THE CONCRETE ROOF TILE. IF AN ADHESIVE WILL |
| | BE USED, SUBMIT TWO SETS OF THE PRODUCT APPROVALS FOR |
| | IT. FBC-R905.3.7 & FBC 107.3.4 |
| | |
| | 12) SHOW COMPLIANCE WITH FBC-R302.12 DRAFTSTOPPING. IN |
| | COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE |
| | BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A |
| | FLOOR/CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED |
| | SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED |
| | 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE |
| | THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. |
| | WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE |
| | ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL |
| | BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE |
| | FOLLOWING CIRCUMSTANCES: |
| | 1. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. |
| | 2. FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB |
| | OR PERFORATED MEMBERS. |
| | |
| | 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |