Plan Review Notes
Plan Review Notes For Permit 17090021
Permit Number 17090021
Review Stop P
Sequence Number 4
Notes
Date Text
2018-02-28 08:47:47DENIED
  
 1. THIS IS THE SECOND REQUEST, SHT.P.1.3.00C SHOWS
 DRINKING FOUNTAIN ON THE LAYOUT AND P.3.1.00C ON THE
 ISOMERIC IS MISSING, ALSO THE RE-VENT FOR THE WASHING
 MACHINE DOES NOT CONNECT, PLEASE RECTIFY. FBC WPB
 AMENDMENTS SEC.107.2.1
  
 2. ADA BATHROOM DOES NOT COMPLY THE REQUIRED CLEARANCE
 AROUND THE WATER CLOSET SHALL BE PERMITTED TO OVERLAP
 THE WATER CLOSET, ASSOCIATED GRAB BARS, DISPENSERS,
 SANITARY NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES,
 ACCESSIBLE ROUTES, CLEAR FLOOR SPACE AND CLEARANCES
 REQUIRED AT OTHER FIXTURES, AND THE TURNING SPACE. NO
 OTHER FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN
 THE REQUIRED WATER CLOSET CLEARANCE. FBC ACC 604.3.2
 OVERLAP. CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL. FBC ACC 604.3.1 SIZE.
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS DETACHED AND MARK
 VOID..\
  