| 2018-02-28 08:47:47 | DENIED |
| | |
| | 1. THIS IS THE SECOND REQUEST, SHT.P.1.3.00C SHOWS |
| | DRINKING FOUNTAIN ON THE LAYOUT AND P.3.1.00C ON THE |
| | ISOMERIC IS MISSING, ALSO THE RE-VENT FOR THE WASHING |
| | MACHINE DOES NOT CONNECT, PLEASE RECTIFY. FBC WPB |
| | AMENDMENTS SEC.107.2.1 |
| | |
| | 2. ADA BATHROOM DOES NOT COMPLY THE REQUIRED CLEARANCE |
| | AROUND THE WATER CLOSET SHALL BE PERMITTED TO OVERLAP |
| | THE WATER CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, |
| | SANITARY NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, |
| | ACCESSIBLE ROUTES, CLEAR FLOOR SPACE AND CLEARANCES |
| | REQUIRED AT OTHER FIXTURES, AND THE TURNING SPACE. NO |
| | OTHER FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN |
| | THE REQUIRED WATER CLOSET CLEARANCE. FBC ACC 604.3.2 |
| | OVERLAP. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| | INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. FBC ACC 604.3.1 SIZE. |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS DETACHED AND MARK |
| | VOID..\ |
| | |