Plan Review Notes
Plan Review Notes For Permit 17090021
Permit Number 17090021
Review Stop P
Sequence Number 3
Notes
Date Text
2018-01-24 10:58:353RD REVIEW: FBC 2014 5TH EDITION
  
  
 PREVIOUS PLUMBING COMMENTS: NOT COMPLIED
  
 2. SHT.A-4.2.02SO THE GRAB BARS SHALL BE SHOWN TO BE
 MEASURED FROM THE GRIPPING SURFACE TO THE FINISHED
 FLOOR. PER FBC ACC 609.4
  
 3. THE COAT HOOK SHALL BE A MAXIMUM OF 48" OF THE
 FINISHED FLOOR PER FBC ACC 308 SHT. A-4.2.02SO SHOWS IT
 AT 54"
  
 4. AS THIS PERMIT IS FOR A BUSINESS OCCUPANCY THE
 BATHING FACILITIES WHICH ARE THE TWO FULL BATHROOMS
 SHALL COMPLY WITH FBC ACC 213 YOU MAY WANT TO REQUEST
 FROM THE BUILDING OFFICIAL SOME RELIEF BY MAKING THESE
 BATHROOM NON USABLE FOR DISPLAY ONLY. THIS CAN BE DONE
 BY WRITING A LETTER TO ROBERT BROWN AND PLACING A NOTE
 ON THE PLAN STATING NON USABLE BATHROOM, WATER NOT TO
 BE CONNECTED TO FIXTURES.
  
  
 NEW COMMENT:
  
 1. THE PLAN SET HAS TWO SHT.P.1.3.00C AND P.3.1.00C ONE
 SHOWS DRINKING FOUNTAIN THE OTHER DOES NOT PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  