| 2018-01-24 10:58:35 | 3RD REVIEW: FBC 2014 5TH EDITION |
| | |
| | |
| | PREVIOUS PLUMBING COMMENTS: NOT COMPLIED |
| | |
| | 2. SHT.A-4.2.02SO THE GRAB BARS SHALL BE SHOWN TO BE |
| | MEASURED FROM THE GRIPPING SURFACE TO THE FINISHED |
| | FLOOR. PER FBC ACC 609.4 |
| | |
| | 3. THE COAT HOOK SHALL BE A MAXIMUM OF 48" OF THE |
| | FINISHED FLOOR PER FBC ACC 308 SHT. A-4.2.02SO SHOWS IT |
| | AT 54" |
| | |
| | 4. AS THIS PERMIT IS FOR A BUSINESS OCCUPANCY THE |
| | BATHING FACILITIES WHICH ARE THE TWO FULL BATHROOMS |
| | SHALL COMPLY WITH FBC ACC 213 YOU MAY WANT TO REQUEST |
| | FROM THE BUILDING OFFICIAL SOME RELIEF BY MAKING THESE |
| | BATHROOM NON USABLE FOR DISPLAY ONLY. THIS CAN BE DONE |
| | BY WRITING A LETTER TO ROBERT BROWN AND PLACING A NOTE |
| | ON THE PLAN STATING NON USABLE BATHROOM, WATER NOT TO |
| | BE CONNECTED TO FIXTURES. |
| | |
| | |
| | NEW COMMENT: |
| | |
| | 1. THE PLAN SET HAS TWO SHT.P.1.3.00C AND P.3.1.00C ONE |
| | SHOWS DRINKING FOUNTAIN THE OTHER DOES NOT PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |