Plan Review Notes
Plan Review Notes For Permit 17090021
Permit Number 17090021
Review Stop P
Sequence Number 2
Notes
Date Text
2017-11-16 16:40:282ND REVIEW: FBC 2014 5TH EDITION
  
  
 PREVIOUS PLUMBING COMMENTS: NOT COMPLIED
  
 4. SHT. P.1.3.00B KEY NOTE #2 SHALL COMPLY WITH FBC PL
 504.6 REQUIREMENTS FOR DISCHARGE PIPING.
 THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE,
 TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL:
 2. DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER.
  
 5. SHT. P.1.3.00B KEY NOTE #5 SHALL COMPLY WITH FBC PL
 802.1.6 DOMESTIC DISHWASHING MACHINES.
 DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2, OR DISCHARGE INTO A WYE-BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER. THE WASTE LINE OF A
 DOMESTIC DISHWASHING MACHINE DISCHARGING INTO A KITCHEN
 SINK TAILPIECE OR FOOD WASTE GRINDER SHALL CONNECT TO A
 DECK-MOUNTED AIR GAP OR THE WASTE LINE SHALL RISE AND
 BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM
 OR COUNTER.
  
 7. THE 4" VENT LOCATED AT THE END OF THE RUN FOR THE
 MASTER BATH TOILET IS A HORIZONTAL DRY VENT WHICH IS
 NOT CODE COMPLAINT THAT VENT IS NOT REQUIRED. PER FBC
 PL 905.3 - 905.5
  
 NEW COMMENTS:
  
 1. THE CLEARANCE FOR THE TOILET SHALL COMPLY WITH FBC
 ACC 604.3.2 THE LAVATORY CAN NOT ENCROACH ON THE 60"
 CLEAR FLOOR SPACE, THE WIDTH OF THE BATHROOM WILL NEED
 TO BE A MIN OF 7' 1" TO ACCOMMODATE THE CLEARANCES.
  
 2. THE GRAB BARS SHALL BE MEASURED FROM THE GRIPPING
 SURFACE TO THE FINISHED FLOOR. PER FBC ACC 609.4
  
 3. THE COAT HOOK SHALL BE A MAXIMUM OF 48" OF THE
 FINISHED FLOOR PER FBC ACC 308
  
 4. AS THIS PERMIT IS FOR A BUSINESS OCCUPANCY THE
 BATHING FACILITIES WHICH ARE THE TWO FULL BATHROOMS
 SHALL COMPLY WITH FBC ACC 213 YOU MAY WANT TO REQUEST
 FROM THE BUILDING OFFICIAL SOME RELIEF BY MAKING THESE
 BATHROOM NON USABLE FOR DISPLAY ONLY. THIS CAN BE DONE
 BY WRITING A LETTER TO ROBERT BROWN AND PLACING A NOTE
 ON THE PLAN STATING NON USABLE BATHROOM, WATER NOT TO
 BE CONNECTED TO FIXTURES.
  
 5. THE LAVATORY IN THE ACCESSIBLE BATHROOM SHALL COMPLY
 WITH FBC PL 416.5 TEMPERED WATER FOR PUBLIC
 HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 6. THE BRANCH FITTINGS IN THE BUILDING DRAIN THAT ARE
 FOR THE DRINKING FOUNTAIN AND KITCHEN ARE SHOWN WITH
 THE DIRECTION OF FLOW FACING THE WRONG DIRECTION ON THE
 RISER AND THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 7. THE VENT FOR THE WATER FOUNTAIN IS SHOWN AS A DRY
 HORIZONTAL DRY VENT THAT IS NOT CODE COMPLIANT THE VENT
 SHOULD CONNECT TO THE TOP OF THE STACK FOR THE WATER
 FOUNTAIN. PER FBC PL 905.3/ 905.4/ 910.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH