| Date |
Text |
| 2017-11-16 16:40:28 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | |
| | PREVIOUS PLUMBING COMMENTS: NOT COMPLIED |
| | |
| | 4. SHT. P.1.3.00B KEY NOTE #2 SHALL COMPLY WITH FBC PL |
| | 504.6 REQUIREMENTS FOR DISCHARGE PIPING. |
| | THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE, |
| | TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL: |
| | 2. DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME |
| | ROOM AS THE WATER HEATER. |
| | |
| | 5. SHT. P.1.3.00B KEY NOTE #5 SHALL COMPLY WITH FBC PL |
| | 802.1.6 DOMESTIC DISHWASHING MACHINES. |
| | DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE |
| | INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK INTO A |
| | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| | 802.2, OR DISCHARGE INTO A WYE-BRANCH FITTING ON THE |
| | TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER |
| | CONNECTION OF A FOOD WASTE GRINDER. THE WASTE LINE OF A |
| | DOMESTIC DISHWASHING MACHINE DISCHARGING INTO A KITCHEN |
| | SINK TAILPIECE OR FOOD WASTE GRINDER SHALL CONNECT TO A |
| | DECK-MOUNTED AIR GAP OR THE WASTE LINE SHALL RISE AND |
| | BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM |
| | OR COUNTER. |
| | |
| | 7. THE 4" VENT LOCATED AT THE END OF THE RUN FOR THE |
| | MASTER BATH TOILET IS A HORIZONTAL DRY VENT WHICH IS |
| | NOT CODE COMPLAINT THAT VENT IS NOT REQUIRED. PER FBC |
| | PL 905.3 - 905.5 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. THE CLEARANCE FOR THE TOILET SHALL COMPLY WITH FBC |
| | ACC 604.3.2 THE LAVATORY CAN NOT ENCROACH ON THE 60" |
| | CLEAR FLOOR SPACE, THE WIDTH OF THE BATHROOM WILL NEED |
| | TO BE A MIN OF 7' 1" TO ACCOMMODATE THE CLEARANCES. |
| | |
| | 2. THE GRAB BARS SHALL BE MEASURED FROM THE GRIPPING |
| | SURFACE TO THE FINISHED FLOOR. PER FBC ACC 609.4 |
| | |
| | 3. THE COAT HOOK SHALL BE A MAXIMUM OF 48" OF THE |
| | FINISHED FLOOR PER FBC ACC 308 |
| | |
| | 4. AS THIS PERMIT IS FOR A BUSINESS OCCUPANCY THE |
| | BATHING FACILITIES WHICH ARE THE TWO FULL BATHROOMS |
| | SHALL COMPLY WITH FBC ACC 213 YOU MAY WANT TO REQUEST |
| | FROM THE BUILDING OFFICIAL SOME RELIEF BY MAKING THESE |
| | BATHROOM NON USABLE FOR DISPLAY ONLY. THIS CAN BE DONE |
| | BY WRITING A LETTER TO ROBERT BROWN AND PLACING A NOTE |
| | ON THE PLAN STATING NON USABLE BATHROOM, WATER NOT TO |
| | BE CONNECTED TO FIXTURES. |
| | |
| | 5. THE LAVATORY IN THE ACCESSIBLE BATHROOM SHALL COMPLY |
| | WITH FBC PL 416.5 TEMPERED WATER FOR PUBLIC |
| | HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 6. THE BRANCH FITTINGS IN THE BUILDING DRAIN THAT ARE |
| | FOR THE DRINKING FOUNTAIN AND KITCHEN ARE SHOWN WITH |
| | THE DIRECTION OF FLOW FACING THE WRONG DIRECTION ON THE |
| | RISER AND THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 7. THE VENT FOR THE WATER FOUNTAIN IS SHOWN AS A DRY |
| | HORIZONTAL DRY VENT THAT IS NOT CODE COMPLIANT THE VENT |
| | SHOULD CONNECT TO THE TOP OF THE STACK FOR THE WATER |
| | FOUNTAIN. PER FBC PL 905.3/ 905.4/ 910.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |