2017-11-12 11:12:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: 2ND REVIEW, ITEMS CORRECTED
 ARE NOTED. REMAINING ITEMS NEED FURTHER CORRECTION, SEE
 ADDITIONAL NOTES IN PARENTHESES.
  
 1. CORRECTED.
 2. CORRECTED.
 3. SERVICE DISCONNECT ON POWER PLAN IS SHOWN AS
 NON-FUSED. OVERCURRENT PROTECTION IS REQUIRED AT THIS
 LOCATION. PROVIDE CORRECTION. NEC 230.91; FBC RE
 3603.3.3 (THERE IS A CONFLICT BETWEEN WHAT IS STATED ON
 POWER PLAN AS 200 AMP FUSES AND THE "UNIT LOAD
 ANALYSIS" WHICH SHOWS A 175 AMP SERVICE WITH 1/0 WIRE.
 1/0 WIRE IS FINE FOR 175 AMP SERVICE, BUT NOT FOR 200
 AMP SERVICE. CLARIFY AND/OR CORRECT.)
 4. CORRECTED.
 5.CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8.CORRECTED.
 9.CORRECTED.
 10. CORRECTED.
 11. THE WATER HEATER SPECIFIED ON SHEET P.0.0.00 IS
 SHOWN WITH 4500 WATT ELEMENTS. THE PANEL SCHEDULE SHOWS
 A 35 AMP BREAKER FOR THIS UNIT, WHICH IS TOO LARGE PER
 CODE. BREAKER SHOULD BE SIZED AT 125% OF THE LOAD,
 WHICH WOULD BE A 25 AMP BREAKER. PROVIDE CORRECTION.
 NEC 422.13; FBC RE3702.10 (WATER HEATER IS NOW SHOWN AS
 6.1 KW, WHICH WOULD REQUIRE A 35 AMP BREAKER, BUT PANEL
 SCHEDULE CALLS FOR A 70 AMP BREAKER. PROVIDE
 CORRECTION.)
 12. CORRECTED.
 13. CORRECTED.
 15. CONDENSING UNIT IS SHOWN BEING FED FROM A 30 AMP
 CIRCUIT TO A 30 AMP DISCONNECT FUSED AT 30 AMPS. SPECS
 ON SHEET M-1 STATE THAT MOCP SHOULD BE 40 AMPS FOR THIS
 UNIT. PROVIDE CORRECTIONS. NEC 440.22(C); FBC RE3702.11
 (DISCONNECT IS SHOWN AS A 30 AMP FRAME WITH 40 AMP
 FUSES. 40 AMP FUSES WILL NOT FIT INTO A 30 AMP FRAME.
 PROVIDE CORRECTION.)
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER