| 2017-11-12 11:12:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: 2ND REVIEW, ITEMS CORRECTED |
| | ARE NOTED. REMAINING ITEMS NEED FURTHER CORRECTION, SEE |
| | ADDITIONAL NOTES IN PARENTHESES. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. SERVICE DISCONNECT ON POWER PLAN IS SHOWN AS |
| | NON-FUSED. OVERCURRENT PROTECTION IS REQUIRED AT THIS |
| | LOCATION. PROVIDE CORRECTION. NEC 230.91; FBC RE |
| | 3603.3.3 (THERE IS A CONFLICT BETWEEN WHAT IS STATED ON |
| | POWER PLAN AS 200 AMP FUSES AND THE "UNIT LOAD |
| | ANALYSIS" WHICH SHOWS A 175 AMP SERVICE WITH 1/0 WIRE. |
| | 1/0 WIRE IS FINE FOR 175 AMP SERVICE, BUT NOT FOR 200 |
| | AMP SERVICE. CLARIFY AND/OR CORRECT.) |
| | 4. CORRECTED. |
| | 5.CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8.CORRECTED. |
| | 9.CORRECTED. |
| | 10. CORRECTED. |
| | 11. THE WATER HEATER SPECIFIED ON SHEET P.0.0.00 IS |
| | SHOWN WITH 4500 WATT ELEMENTS. THE PANEL SCHEDULE SHOWS |
| | A 35 AMP BREAKER FOR THIS UNIT, WHICH IS TOO LARGE PER |
| | CODE. BREAKER SHOULD BE SIZED AT 125% OF THE LOAD, |
| | WHICH WOULD BE A 25 AMP BREAKER. PROVIDE CORRECTION. |
| | NEC 422.13; FBC RE3702.10 (WATER HEATER IS NOW SHOWN AS |
| | 6.1 KW, WHICH WOULD REQUIRE A 35 AMP BREAKER, BUT PANEL |
| | SCHEDULE CALLS FOR A 70 AMP BREAKER. PROVIDE |
| | CORRECTION.) |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | 15. CONDENSING UNIT IS SHOWN BEING FED FROM A 30 AMP |
| | CIRCUIT TO A 30 AMP DISCONNECT FUSED AT 30 AMPS. SPECS |
| | ON SHEET M-1 STATE THAT MOCP SHOULD BE 40 AMPS FOR THIS |
| | UNIT. PROVIDE CORRECTIONS. NEC 440.22(C); FBC RE3702.11 |
| | (DISCONNECT IS SHOWN AS A 30 AMP FRAME WITH 40 AMP |
| | FUSES. 40 AMP FUSES WILL NOT FIT INTO A 30 AMP FRAME. |
| | PROVIDE CORRECTION.) |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |