| 2017-09-27 18:02:09 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. AT LEAST ONE OF THE BATHROOMS SHALL BE MADE FULLY |
| | ACCESSIBLE. PER FBC ACC 213.1 |
| | |
| | 2. THE ACCESSIBLE BATHROOM SHALL COMPLY WITH THE |
| | FOLLOWING CODE SECTIONS. FBC ACC 603, 604, 606 , 609 |
| | PLEASE PROVIDE DIMENSIONS AND SHOW CLEAR FLOOR SPACE ON |
| | THE PLANS . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. PLEASE SHOW COMPLIANCE OF WATER FOUNTAIN PER .FBC |
| | ACC 602 |
| | |
| | 4. SHT. P.1.3.00B KEY NOTE #2 SHALL COMPLY WITH FBC PL |
| | 504.6 REQUIREMENTS FOR DISCHARGE PIPING. |
| | THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE, |
| | TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL: |
| | 2. DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME |
| | ROOM AS THE WATER HEATER. |
| | |
| | 5. SHT. P.1.3.00B KEY NOTE #5 SHALL COMPLY WITH FBC PL |
| | 802.1.6 DOMESTIC DISHWASHING MACHINES. |
| | DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE |
| | INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK INTO A |
| | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| | 802.2, OR DISCHARGE INTO A WYE-BRANCH FITTING ON THE |
| | TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER |
| | CONNECTION OF A FOOD WASTE GRINDER. THE WASTE LINE OF A |
| | DOMESTIC DISHWASHING MACHINE DISCHARGING INTO A KITCHEN |
| | SINK TAILPIECE OR FOOD WASTE GRINDER SHALL CONNECT TO A |
| | DECK-MOUNTED AIR GAP OR THE WASTE LINE SHALL RISE AND |
| | BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM |
| | OR COUNTER. |
| | |
| | 6. SHT. P.1.3.00B KEY NOTE #6 SHALL COMPLY WITH FBC PL |
| | 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION. |
| | THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. THE JUNCTION OF |
| | THE BUILDING DRAIN AND SEWER SHALL BE 30" MAX FROM |
| | BUILDING. 15' DOES NOT COMPLY. |
| | |
| | 7. THE 4" VENT LOCATED AT THE END OF THE RUN FOR THE |
| | MASTER BATH TOILET IS A HORIZONTAL DRY VENT WICH IS NOT |
| | CODE COMPLAINT THAT VENT IS NOT REQUIRED. PER FBC PL |
| | 905.3 - 905.5 |
| | |
| | 8. PLEASE LABEL ALL FIXTURES ON WATER RISER. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |