| 2017-09-25 17:53:43 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17090021 |
| | 9/25/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE M1 HVAC FLOOR PLAN SHOWING A LAYOUT FOR A |
| | 3-BEDROOM HOUSE DOES NOT MATCH THE ARCHITECTURAL FLOOR |
| | AND RCP PLANS WHICH INDICATE THE HOUSE WILL BE |
| | CONVERTED TO A SALES OFFICE CENTER. PLEASE PROVIDE |
| | CORRECT ROOM IDENTIFCATION LABELS ON THE PLAN. |
| | |
| | 2) PROVIDE VENTILATION CALCULATIONS FOR ALL OCCUPIED |
| | ROOMS AND SPACES USING EITHER NATURAL VENTILATION PER |
| | SECTION 402, OR MECHANICAL PER SECTION 403. |
| | |
| | 3) SALES OFFICES ARE BUSINESS OCCUPANCIES AND FALL |
| | UNDER THE COMMERCIAL PROVISIONS OF THE FLORIDA ENERGY |
| | CONSERVATION CODE- 2014: A) REFER TO SECTION C403.2.1 |
| | AND PROVIDE AC COOLING AND HEATING CALCULATIONS IN |
| | ACCORDANCE WITH ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL |
| | N. B) THE SUBMITTED ENERGY CALCULATION FORM R405-2014 |
| | CAN NOT BE USED TO SHOW COMPLIANCE FOR A COMMERCIAL |
| | BUILDING. REFER TO SECTION C101.5.1 AND PROVIDE A |
| | COMMERCIAL COMPLIANCE SUBMITTAL. |
| | |
| | 4) THE M1 PLAN SHEET NEEDS TO BE PLACED IN THE PLAN |
| | SETS PROPERLY SO THAT ALL INFORMATION CAN BE READ. THE |
| | CURRENT SHEET IS STAPLED TO CLOSE TO THE LEFT MARGIN |
| | MAKING SOME OF THE NOTES AND DETAILS UNABLE TO BE READ |
| | AND REVIEWED- PLEASE FIX THE PROBLEM- SECTION 107 WPB |
| | AMENDMENTS TO THE FBC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |