| 2017-11-16 16:43:09 | 4TH REVIEW FBC-2014 MECHANICAL |
| | PERMIT #170I90016 |
| | 11/16/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PLANS WERE RESUBMITTED WITHOUT ANY CORRECTIONS |
| | OR RESPONSES TO THE PREVIOUS MECHANICAL REVIEW |
| | COMMENTS. I HAVE REPINTED THE COMMENTS BELOW- PLEASE |
| | COMPLY. |
| | |
| | 1) REFER TO SECTION 506.3.11.2 FIELD APPLIED GREASE |
| | DUCT ENCLOSURE FBC-14 MECHANICAL: "THE SURFACE OF THE |
| | DUCT SHALL BE CONTINUOUSLY COVERED ON ALL SIDES FROM |
| | THE POINT AT WHICH THE DUCT ORIGINATES TO THE OUTLET |
| | TERMINAL." "PARTIAL APPLICATION OF A FIELD-APPLIED |
| | GREASE DUCT ENCLOSURE SYSTEM SHALL NOT BE INSTALLED FOR |
| | THE SOLE PURPOSE OF REDUCING CLEARANCES TO COMBUSTIBLES |
| | AT ISOLATED SECTIONS OF GREASE DUCT." IT APPEARS BY |
| | THIS SECTION THAT THE DUCT WRAPPING AS SHOWN ON THE |
| | PLAN IS NOT BEING INSTALLED IN ACCORDANCE WITH THE ASTM |
| | E 2336 LISTING. ADDITIONAL INFORMATION FROM THE PRODUCT |
| | MANUFACTURER WILL BE REQUIRED, AS WELL AS EVIDENCE THAT |
| | THE INSTALLATION AS SHOWN DOES NOT VOID THE UL LISTING. |
| | PLEASE NOTE THAT SECTION 506.3.6 PERMITS A 3" CLEARANCE |
| | TO NON-COMBUSTIBLE CONSTRUCTION AND GYPSUM WALL BOARD |
| | ATTACHED TO NON-COMBUSTIBLE STRUCTURES. |
| | |
| | 2) REFER TO SECTION 8.1.3.6 NFPA 96 REGARDING THE |
| | INLINE FAN: WHERE THE DUCT SYSTEM CONNECTED TO THE FAN |
| | IS IN AN ENCLOSURE, THE SPACE OR ROOM IN WHICH THE |
| | EXHAUST FAN IS LOCATED SHALL HAVE THE SAME FIRE |
| | RESISTANCE RATING AS THE ENCLOSURE. ACCORDING TO THIS |
| | SECTION, THE FAN MUST BE IN A FIRE-RATED ROOM. |
| | |
| | 3) IN RESPONSE TO PREVIOUS REVIEW COMMENT #3, THE HOOD |
| | DESIGNER IS STATING THAT THE ADDED HEATING AND COOLING |
| | LOADS OF THE MUA (MAKEUP AIR) DO NOT EXCEED THE |
| | CAPACITY OF THE AC SYSTEM. PLEASE PROVIDE ACTUAL |
| | EVIDENCE IN THE FORM OF CALCULATIONS, DETAILS ETC. TO |
| | SUPPORT AND PROVE THIS CLAIM. |
| | |
| | 4) PROVIDE A DETAILL SHOWING HOW GREASE FROM THE INLINE |
| | FAN WILL BE DISPOSED OF PROPERLY. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |