| Plan Review Notes For Permit 17090013 |
| Permit Number |
17090013 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-01 16:19:57 | 1ST REVIEW FBC-2014 BUILDING | | | PERMIT #17090013 | | | 9/1/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED ENGINEERING FROM FEDERAL ENGINEERING & | | | TESTING INDICATES A 4' PARAPET ON THE BUILDING WHICH | | | ALLOWS ZONE 3 (CORNERS) TO BE TREATED AS ZONE 2 ( | | | PERIMETER) IN TERMS OF FASTENER DENSITIES, HOWEVER THE | | | BUILDING DOES NOT HAVE A PARAPET SO THE THE FASTENER | | | DENSITIES SHALL BE INCREASED FOR THE CORNERS. PLEASE | | | PROVIDE CORRECTED ENGINEERING. | | | | | | 2) PLEASE INDICATE IN THE NOA WHICH OF THE THREE TPO | | | SYSTEMS WILL BE INSTALLED. | | | | | | CHRISTOPHER L. COLE | | | BUILDING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|