2017-09-29 15:47:30DENIED 9/29/17 LAC
  
 1. THE SHOWER IS SIZED AS A 3? PER CODE A 2? IS THE
 MINIMUM, HOW MANY DFU?S (GPM) IS THE SHOWER HEAD TO
 DRAIN TO THE SHOWER. FBC P3004.1, P3201.7
  
 2. PLANS CALL FOR A STEAM SHOWER PLEASE PROVIDE
 LOCATION AND SPECIFICATION FOR STEAM GENERATOR, PLEASE
 PROVIDE MANUFACTURE SPECIFICATION. IF THE STEAM UNIT IS
 UNDER A THE SHOWER SEAT. HOW IS THE STEAM ENTERING THE
 SHOWER? PLEASE CLARIFY WHAT TYPE OF PROTECTION IS BEING
 USED AND SHOW WHERE IT GOING IN THE SHOWER. FBC
 AMENDMENTS 107.2.1A-2
  
 3. SHOWER PAN IS NOT RECEDED IT WILL REQUIRE LINING FBC
 P2709.2
  