Plan Review Notes
Plan Review Notes For Permit 17090002
Permit Number 17090002
Review Stop G
Sequence Number 1
Notes
Date Text
2017-09-29 15:56:14FAILED 9/29/17 LAC
  
 1. NEED SEPARATE PERMIT FOR GAS IS REQUIRED FBC A 105.3
  
 2. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
 3. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THOUGH
 THE EXTERIOR WILL BE PROTECTED. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH FBC-2014 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 5. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. FGC
 SEC.304.9.3 OR FBCR G2407.9.3.
  
 6. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
  
 7. THE BTU LOAD OF THE GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE FUTURE GAS SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. THE LOAD OF THE
 FUTURE RANGE IN NOT CALCULATED ON THE GAS PIPING
 ISOMETRIC PAGE P-1. IF UNDERSIZED, THE EXISTING SYSTEM
 MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. FGC
 SEC. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 8. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE RANGE
 SHOW ON GAS ISOMERIC P-1 APPLIANCE SHUTOFF IFGC 409.5,
 APPLIANCE CONNECTION IFGC 404.15, 411.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  