| 2017-09-29 15:56:14 | FAILED 9/29/17 LAC |
| | |
| | 1. NEED SEPARATE PERMIT FOR GAS IS REQUIRED FBC A 105.3 |
| | |
| | 2. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1. |
| | |
| | 3. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THOUGH |
| | THE EXTERIOR WILL BE PROTECTED. WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1. |
| | |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH FBC-2014 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1. |
| | |
| | 5. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR. FGC |
| | SEC.304.9.3 OR FBCR G2407.9.3. |
| | |
| | 6. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL |
| | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, |
| | G2412.8, G2413.1, G2413.2, & G2413.3. |
| | |
| | 7. THE BTU LOAD OF THE GAS SYSTEM MUST BE ADDED INTO |
| | THE TOTAL BTU LOAD ON THE FUTURE GAS SYSTEM TO ENSURE |
| | THE EXISTING SYSTEM IS PROPERLY SIZED. THE LOAD OF THE |
| | FUTURE RANGE IN NOT CALCULATED ON THE GAS PIPING |
| | ISOMETRIC PAGE P-1. IF UNDERSIZED, THE EXISTING SYSTEM |
| | MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. FGC |
| | SEC. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | |
| | 8. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE RANGE |
| | SHOW ON GAS ISOMERIC P-1 APPLIANCE SHUTOFF IFGC 409.5, |
| | APPLIANCE CONNECTION IFGC 404.15, 411. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |