| 2017-09-26 11:19:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12 |
| | 2. LIGHTING IN MASTER CLOSETS SHOWS STANDARD RECESS |
| | LIGHTS. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY |
| | ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS |
| | SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE |
| | CORRECTION. NEC 410.16; FBC RE4003.12 |
| | 3. PANEL SCHEDULE SHOWS A 50 AMP BREAKER FOR THE NEW |
| | AHU AND A 30 AMP BREAKER FOR THE NEW CU. SPECS ON THE |
| | MECHANICAL SHEETS REQUIRE A 30 AMP BREAKER FOR THE AHU |
| | AND A 25 AMP BREAKER FOR THE CU. PROVIDE CORRECTION. |
| | THE BRANCH CIRCUIT OVERCURRENT PROTECTION DEVICE RATING |
| | SHALL BE THE SIZE AND TYPE MARKED ON THE EQUIPMENT. NEC |
| | 440.22(C); FBC RE3702.11 |
| | 4. PROVIDE PANEL SCHEDULE FOR PANEL A, INDICATING ANY |
| | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 215.5, 408.4; FBC RE3706.2, RE3902 |
| | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 6. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS |
| | REQUIRED WITHIN 3 FEET OF EACH BASIN IN MASTER BATH. |
| | PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| | 3703.4, 3901.6 |
| | 7. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15 |
| | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION. A NOTE WILL |
| | SUFFICE. NEC 210.12; FBC RE3902.12 |
| | 8. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC CE R404.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |