2017-09-18 10:04:401ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17081495
 9/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M2.1: IDENTIFY THE PURPOSE OF THE DUCTWORK
 REPRESENTED BY DOTTED LINES ON THE PLAN AND LABELED AS
 "EXISTING". ARE THESE RETURN AIR DUCTS OR OUTSIDE AIR
 DUCTS? PLEASE NOTE THAT THE TRASH ROOM IS A PROHIBITED
 SOURCE OF RETURN AIR PER SECTION 918.6 ITEMS #2 AND 5,
 AND ALSO A PROHIBITED SOURCE OF OUTSIDE AIR PER SECTION
 401.4 ITEM #2. ADDITIONALLY, RETURN AIR SHALL NOT BE
 TAKEN FROM
 THE ADJACENT OCCUPANCY PER SECTION 601.5 FBC-14
 MECHANICAL, AND SECTION C402.4.9 FBC-14 ENERGY
 CONSERVATION.
  