| Plan Review Notes For Permit 17081495 |
| Permit Number |
17081495 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-18 10:04:40 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17081495 | | | 9/18/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M2.1: IDENTIFY THE PURPOSE OF THE DUCTWORK | | | REPRESENTED BY DOTTED LINES ON THE PLAN AND LABELED AS | | | "EXISTING". ARE THESE RETURN AIR DUCTS OR OUTSIDE AIR | | | DUCTS? PLEASE NOTE THAT THE TRASH ROOM IS A PROHIBITED | | | SOURCE OF RETURN AIR PER SECTION 918.6 ITEMS #2 AND 5, | | | AND ALSO A PROHIBITED SOURCE OF OUTSIDE AIR PER SECTION | | | 401.4 ITEM #2. ADDITIONALLY, RETURN AIR SHALL NOT BE | | | TAKEN FROM | | | THE ADJACENT OCCUPANCY PER SECTION 601.5 FBC-14 | | | MECHANICAL, AND SECTION C402.4.9 FBC-14 ENERGY | | | CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|