2017-09-19 08:45:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS 3/0 WIRE ON A 225 AMP BREAKER
 FEEDING PANEL A. 3/0 WIRE IS NOT RATED FOR 225 AMPS.
 PROVIDE CORRECTION. NEC 310.15(B)(16)
 2. PROVIDE NOTE THAT ANY LOW VOLTAGE WORK, INCLUDING
 FIRE ALARM, WILL BE UNDER SEPARATE PERMIT. FBC 105.1
 3. PLAN SHOWS ADDRESS AS 300 23RD ST., WHILE PERMIT
 APPLICATION SHOWS THE ADDRESS AS 304 23RD ST. PROVIDE
 CORRECT ADDRESS ON PLANS. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  