2017-09-26 14:45:451ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 THE EEMAX SP241DL
 DOES NOT COMPLY THE EEMAX ACCUMIX SERIES DOES SUCH AS
 THE MB004120T, YOU CAN ALSO USE A SEPARATE
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 . PER FBC PL 416.5
  
 2. SHT. 3 WATER HEATER DETAIL THE DISCHARGE PIPING
 SERVING A PRESSURE RELIEF VALVE, TEMPERATURE RELIEF
 VALVE OR COMBINATION THEREOF SHALL DISCHARGE THROUGH AN
 AIR GAP LOCATED IN THE SAME ROOM AS THE WATER HEATER
 AND DISCHARGE TO A TERMINATION POINT THAT IS READILY
 OBSERVABLE BY THE BUILDING OCCUPANTS. PER FBC PL 504.6
  
 3. SHT. 3 WATER HEATER DETAIL THE PAN SHALL BE DRAINED
 BY AN INDIRECT WASTE PIPE HAVING A DIAMETER OF NOT LESS
 THAN 3/4 INCH. PER FBC 504.7.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  