| 2017-09-15 15:52:43 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE - BUILDING INSPECTOR |
| | 561-805-6667 [email protected] |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| | RESIDENTIAL CODE 2015 5TH EDITION |
| | |
| | 1. BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT |
| | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. |
| | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE |
| | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN |
| | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP |
| | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE |
| | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN |
| | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY |
| | IMPACT FEES AT (561) 233-5025. |
| | |
| | 2. PROVIDE TWO COMPLETE SETS OF PRODUCT APPROVALS. |
| | FBC 107.3.4 , FBC 107.1 - PROVIDE PRODUCT APPROVALS FOR |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD. SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR |
| | SUBMITTALS. |
| | |
| | 3. DOORS AND WINDOWS ON SCHEDULE ARE NOT SHOWN ON THE |
| | FLOOR PLAN. |
| | |
| | 4. ACCORDIAN SHUTTER SCHEDULE DOES NOT HAVE SHUTTERS |
| | LISTED. THERE IS A NOA FOR WINDOWS LISTED HERE. NOA?S |
| | PROVIDED ARE FOR IMPACT PRODUCTS. PLEASE CONFIRM. |
| | |
| | 5. PROVIDE SIZE OF EXISTING BEDROOM WINDOW TO CONFIRM |
| | THAT IT MEETS THE REQUIREMENTS OF A EMERGENCY ESCAPE |
| | RESCUE OPENING. R310.1 |
| | |
| | 6. EXISTING BEAM BEING CONVERTED INTO A TIE BEAM |
| | CREATES A FEW CONCERNS. |
| | |
| | A. BY ENCASING THE EXISTING 2 X 8 IN CONCRETE CREATES |
| | ISSUES WITH WOOD DECAY. R317 |
| | |
| | B. THE 4 - #5 BARS WILL NOT HAVE REQUIRED COVERAGE. |
| | R611.5.4.1 R611.5.4.2 |
| | |
| | C. ARE LINTELS USED OVER OPENINGS. PROVIDE A SCHEDULE. |
| | R611.8.2 |
| | |
| | D. VERTICAL BARS APPEAR TO BE GOING INTO EXISTING BEAM. |
| | HOOK BARS ARE NOT SHOWN. PROVIDE A DETAIL. FBC107.2.1 |
| | |
| | 7. FIELD VERIFY THAT THERE IS AN EXISTING FOOTING AND |
| | PROVIDE THE SIZE. FBC107.3 |
| | |