2017-09-14 14:06:57FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 BRANCH CIRCUIT OCP IS NOT FIGURED FOR CONTINUOUS LOAD
 FACTOR FROM 210.20(A)
  
 CIRCUIT FIGURED OUT TO 19.5 AMPERES FOR THE TOTAL
 LIGHTING LOAD.
  
  
  