| Plan Review Notes For Permit 17081420 |
| Permit Number |
17081420 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-14 14:06:57 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | BRANCH CIRCUIT OCP IS NOT FIGURED FOR CONTINUOUS LOAD | | | FACTOR FROM 210.20(A) | | | | | | CIRCUIT FIGURED OUT TO 19.5 AMPERES FOR THE TOTAL | | | LIGHTING LOAD. | | | | | | | | | |
|