| Plan Review Notes For Permit 17081411 |
| Permit Number |
17081411 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-13 15:11:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | | | | 1) THERE IS LIMITED DETAIL PROVIDED INDICATING WHERE | | | THIS GATE IS LOCATED AND WHETHER IT IS ENTRY OR EGRESS | | | OR BOTH. | | | | | | PLEASE PROVIDE A DETAILED SITE PALN AND VEHICLE PATH OF | | | TRAVEL DIRECTION. | | | | | | | | | | | | 2) THERE IS INSUFFICIENT INFORMATION PROVIDED TO REVIEW | | | REGARDING HOW THE GATE(S) WILL FUNCTION FOR AN | | | EMERGENCY VEHICLE. | | | | | | PLEASE PROVIDE AN EXPLANATION. A KNOX KEY SWITCH MAY BE | | | REQUIRED IF ACCESS/EGRESS IS CONTROLLED. | | | | | | | | | | | | 3) NEW DELINIATORS ARE INDICATED, THOUGH IT IS NOTED AS | | | CUSTOMER PROVIDED, INFORMATION ON THESE NEEDS TO BE | | | PROVIDED; WHAT TYPE, SIZE, ETC. | | | | | | PLEASE PROVIDE SPEC SHEETS. | | | | | | | | | | | | | | | 4) THERE ARE NO INDICATIONS OF THE DIMENSION/WIDTH OF | | | THE TRAVEL LANE BETWEEN THE MEDIUM AND THE NEW | | | DELINIATORS. | | | | | | FOR EMERGECNY VEHILES ACCESS IT MUST BE 20' MINIMUM. | | | | | | PLEASE PROVIDE DIMENSION ON THE SITE PLAN | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|