Plan Review Notes
Plan Review Notes For Permit 17081347
Permit Number 17081347
Review Stop G
Sequence Number 1
Notes
Date Text
2017-09-07 10:30:44SHOW THE DISTANCE FROM DRIVEWAY. WHAT KIND OF
 PROTECTION WILL BE USED, PLEASE PROVIDE DETAILS ON TYPE
 OF METHOD. NFPA 58 SEC. 6.6.6.1.(B)
  
 THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY
 WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF
 THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE.
  
 THE TABLE SUBMITTED FOR 2 PSI INLET PRESSURE DOES NOT
 INDICATE THE TYPE OF PIPE THE TABLE IS FOR. WHAT IS THE
 TABLE NUMBER? PLEASE REFER TO THE EDITION IN EFFECT
 WHICH IS 2011 EDITION FBC 2014 > NFPA 2011
  
 REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
  
 ENGINEERS SEAL AND SIGNATURE IS A COPY, PLEASE SUPPLY
 TWO COPIES WITH AN INK SEAL AND ORIGINAL SIGNATURE OF
 THE ENGINEER. F.A.C. RULE 61 G15-23.001, 23,002
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 561-805-6720
 [email protected]
  