| 2018-01-24 15:15:50 | 3RD REVIEW FBC-2014 RESIDENTIAL MECHANICAL |
| | PERMIT #17081337 |
| | 1/24/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) NEW MECHANICAL PLANS HAVE BEEN SUBMITTED HOWEVER NO |
| | REVISED ENERGY OR AC LOAD CALCULATIONS HAVE BEEN |
| | SUBMITTED. OF THE TWO PREVIOUS SETS THAT WERE |
| | SUBMITTED, ONE SET IS ON AN OUTDATED 2010 ENERGYGAUGE |
| | FORM, AND THE SECOND SET HAS BEEN VOIDED OUT. PLEASE |
| | SUBMIT REVISED CALCULATIONS. |
| | |
| | 2) SHEET M.1: THE MAIN PLANS FOR THE PROJECT SHOW THE |
| | AC CLOSET DOOR 5D IS A SOLID CORE WOOD DOOR, HOWEVER |
| | THE AC PLANS INDICATE AIR WILL BE RETURNED THROUGH THE |
| | DOORS- PLEASE CORRECT. |
| | |
| | 3) M.1: PROVIDE A EXHAUST VENTILATION PLAN FOR THE |
| | KITCHEN- SEE TABLE M1507.4 FOR EXHAUST RATES- 100 CFM |
| | INTERMITTENT OR 25 CFM CONTINUOUS. PLEASE NOTE THAT |
| | RANGE HOODS SHALL COMPLY WITH SECTIONS M1503. |
| | |
| | 4) M.1: THE AC PLAN SHOWS NO AIR PROVIDED TO THE HALL |
| | AND FOYER. SEE COMMENT #1 ABOVE AND PROVIDE AC |
| | CALCUATIONS INCLUDING THE MANUAL J WORKSHEET. |
| | |
| | 5) M.1: PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF |
| | THE CONDENSER PADS AND MOUNTING THE CONDENSERS TO THE |
| | PADS. |
| | |
| | 6) M.1 & M.2: PROVIDE CONDENSATE DISPOSAL PLANS- |
| | SECTION M1411.3. |
| | |
| | 7) M.2: PROVIDE A DRYER EXHAUST PLAN- SEE SECTION |
| | M1502. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |