Plan Review Notes
Plan Review Notes For Permit 17081253
Permit Number 17081253
Review Stop P
Sequence Number 1
Notes
Date Text
2017-09-25 16:01:171ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. C-102 THE NOTES ON THE PLAN TO REINSTALL
 BACKFLOW AND WATER METER REF. P-103 THERE ARE NO
 DETAILS FOR THE BACK FLOW OR WATER METER PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE PROVIDE NOTE ON PLAN STATING THAT A SEPARATE
 PERMIT IS REQUIRED FOR THE BACKFLOWS PROVIDE
 MANUFACTURE SPEC SHEETS FOR EXISTING AND NEW BACKFLOW
 DEVISES. PER WPB UTILITIES DEPT.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  