| 2017-08-30 10:44:42 | 4396 EASLEY DRIVE - DEWATERING BUILDING |
| | FS PERMIT #17081240 |
| | UGFIRELINE: #16020206 |
| | BUILDING MASTER #15060563 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PLANS DO NOT INDICATE AN ADDRESS FOR THE FACILITY. |
| | |
| | THE PERMIT VALUE OF $15,000 IS UNDERVALUED FOR THE |
| | SCOPE OF THE PROJECT. PERMIT VALUES SHALL INCLUDE BOTH |
| | LABOR AND MATERIALS. SUBMIT A COPY OF THE SIGNED |
| | CONTRACT INDICATING VALUE. |
| | |
| | THE UNDERGROUND FIRE MAIN (PERMIT #16020206) DOES NOT |
| | SHOW A SUPPLY TO A FIRE PUMP AND NO REVISION WAS EVER |
| | SUBMITTED SHOWING THIS CHANGE. THIS PERMIT HAS BEEN |
| | CLOSED. A SEPARATE UNDERGROUND PERMIT WILL BE NEEDED BY |
| | A FLORIDA STATE FIRE PROTECTION CONTRACTOR FOR THIS |
| | UNDERGROUND WORK. |
| | |
| | THE FIRE SPRINKLER SYSTEM DESIGN CANNOT BE VERIFIED |
| | WITHOUT THE FIRE PUMP AND PUMP HOUSE SUBMITTALS. WHAT |
| | CONTRACTOR IS BUYING AND INSTALLING THE PUMP AND HOUSE? |
| | IS THE ELECTRICAL SERVICE FOR THE FIRE PUMP, JOCKEY |
| | PUMP AND CONTROLLERS PERMITTED? |
| | |
| | STANDPIPE PROVIDED FOR EXTERIOR EGRESS STAIR. |
| | |
| | CLOSELY SPACED SPRINKLER DEMAND NOT FOUND IN ANY |
| | HYDRAULIC CALCULATIONS. |
| | |
| | SUBMIT THE SAFETY DATA SHEET JUSTIFYING SPRINKLER |
| | PROTECTION IS NOT REQUIRED IN THE ELEVATOR PIT |
| | UTILIZING NON-COMBUSTIBLE HYDRAULIC OIL. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |