| Plan Review Notes For Permit 17081239 |
| Permit Number |
17081239 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-11-06 09:29:57 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | COMMENT FROM PREVIOUS REVIEW: | | | | | | 1. FBC A 223.1, NO ACCESSIBILITY DETAILS WERE PROVIDED. | | | IS A SIMILAR ACCESSIBLE SUITE ALREADY AVAILABLE? PLEASE | | | READ THE ADVISORY, REVISE PLAN TO COMPLY WITH | | | APPLICABLE ACCESSIBLE DETAILS AND DESIGN OR, BEFORE | | | RESUBMITTING, PROVIDE RATIONALE FOR CONSTRUCTING A | | | NON-ACCESSIBLE SUITE. | | | | | | 2ND REVIEW: | | | | | | THE RESPONSE LETTER INCLUDES AN OVERALL PLAN OF THIS | | | PORTION OF THE FLOOR AS WELL AS INDICATION OF AN | | | ACCESSIBLE UNIT. IT IS NOT CLEAR HOW MANY TOTAL UNITS, | | | HOW MANY ACCESSIBLE UNITS NOR WHETHER A SUITE OF THIS | | | TYPE IS AVAILABLE. | | | | | | SEE FBC A ADVISORY 223.1.1 AND SECTION FBC A 223.1.1. | | | SEE ALSO FBC A 223.2. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS. | | | OR, PLEASE SEND LETTER AND/OR INFORMATIONAL PLAN VIA | | | EMAIL FOR PRELIMINARY REVIEW (WILL ALSO VERIFY WITH | | | PLUMBING THAT PROPOSED INFORMATION IS ACCEPTABLE). | | | | | | | | | | | | |
|