Plan Review Notes
Plan Review Notes For Permit 17081236
Permit Number 17081236
Review Stop P
Sequence Number 1
Notes
Date Text
2017-10-03 09:47:331ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 4. ON THE SANITARY ISOMETRIC DRAWING IT SHOWS THE
 BRANCH DRAIN FOR THE FLOOR DRAIN IN PANTRY AS 3"
 CONNECTING TO A 2" . PIPING CAN NOT BE REDUCED IN
 DIRECTION OF FLOW. PER FBC PL 704.2
  
 5. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 6. PLEASE SIZE ENTIRE LENGTH OF THE BUILDING DRAIN, THE
 SANITARY SIZING CALCULATIONS ON SHT P1.1 SHOWS 4" THE
 ISOMETRIC DRAWING ONLY SHOWS 3" PLEASE CLARIFY. SHALL
 COMPLY WITH FBC PL TABLE 710.1(1)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  