| 2017-09-13 13:00:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS, |
| | FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, |
| | WALK-IN COOLERS, HOODS, ETC. FBC 105.1 |
| | 2. RECEPTACLE CONTROL INDICATED DOES NOT COVER ALL |
| | AREAS REQUIRED. PROVIDE CORRECTION TO INCLUDE CONTROL |
| | FOR AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP |
| | RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS, |
| | ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING |
| | FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL |
| | WORKSTATIONS. FBC CE 405.7.1, ASHRAE 90.1:8.4.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |