| 2017-08-29 11:36:34 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. GRAB BARS SHALL BE MEASURED FROM TOP OF GRIPPING |
| | SURFACE TO FINISH FLOOR. PER FBC ACC 609.4 |
| | |
| | 2. SHT. A2.1 DETAILS 2, 5, 9, AND UNDER KEY NOTE |
| | DETAILS 8, 9 SHOW VERTICAL GRAB BARS, GRAB BARS SHALL |
| | BE INSTALLED IN A HORIZONTAL POSITION ONLY. PER FBC ACC |
| | 609.4 |
| | |
| | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.6 FLUSH |
| | CONTROLS. |
| | FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET |
| | |
| | 4. PLEASE EXPAND THE WATER RISER AND LABEL ALL |
| | FIXTURES. WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 5. THE RPZ BACKFLOW DEVISE ON WATER SERVICE SHALL BE |
| | NEXT TO THE CITY METER PER WPB UTILITIES DEPT. |
| | |
| | 6. A SEPARATE PERMIT IS REQUIRED FOR THE RPZ ON THE |
| | WATER SERVICE. |
| | |
| | 7. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FOR |
| | GREASE INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1. |
| | |
| | 8. PLEASE PROVIDE A SANITARY RISER. PER WPB AMEND TO |
| | FBC 107.3.5.1.3(13) |
| | |
| | 9. PLEASE SHOW ON THE RISER DIAGRAMS THE REQUIRED TRAP |
| | PRIMERS ON FLOOR DRAINS, THE AIR HAMMER ARRESTORS AND |
| | SHUT OFFS ON THE DROPS. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |