| 2017-08-30 08:58:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NOT |
| | INDICATED ON POWER PLAN. NEC 600.5; FBC CE 405.2.4 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION. MANY ITEMS ARE |
| | LISTED IN PANEL SCHEDULES AND SHOW 0.00 KVA LOAD. |
| | UPDATE ALL SCHEDULES WITH ACCURATE INFORMATION TO SHOW |
| | TOTAL LOAD ON SERVICE. NEC 220; FBC 107.2.1 |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 4. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS. |
| | NEC 110.3, 110.9 |
| | 5. PROVIDE GFCI PROTECTED W/P OUTLET FOR SERVICING OF |
| | A/C EQUIPMENT ON ROOF PER CODE. NEC 210.63 |
| | 6. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV, |
| | PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS, |
| | HOODS, ETC. FBC 105.1 |
| | 7. IN THE BATHROOMS AND BOH AREAS, IS THE SWITCH |
| | INDICATED AN OCCUPANCY SENSOR TYPE SWITCH? NO NOTE OR |
| | LEGEND IS PROVIDED. PROVIDE CLARIFICATION. FBC 107.2.1 |
| | 8. DETAIL 5 ON SHEET E2.0 SHOWS CIRCUITS CONTROLLED |
| | THAT ARE NOT ON ANY OF THE PLANS. PROVIDE CORRECTION. |
| | FBC 107.2.1 |
| | 9. CIRCUIT L-17 DOES NOT SHOW ANY MANUAL OR AUTOMATIC |
| | CONTROL FOR THE LIGHTING. PROVIDE CORRECTION. FBC CE |
| | 405.2.2 |
| | 10. PROVIDE COPY OF SIGNED CONTRACT, WITH SCOPE AND |
| | VALUE OF WORK SHOWN. FBC 109.3 |
| | |
| | PLEASE NOTE: IT APPEARS THERE IS QUITE A LOT OF MISSING |
| | INFORMATION WITH THIS SUBMITTAL. SUBMITTAL OF |
| | ADDITIONAL AND/OR REVISED MATERIALS MAY RESULT IN NEW |
| | PLAN REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL |
| | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE CITY RESUBMITTAL FORM. ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO THE ORIGINAL SUBMITTAL AND REMOVE |
| | OR VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |