| 2017-11-09 11:11:56 | 2010 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17081172 WINDOW/ DOOR SUBMITTAL |
| | LEVELS 5-24 |
| | W. P. B. PERMIT: 15111020 BUILDING PERMIT |
| | ADD: 1100 S. FLAGLER DR. |
| | CONT: SUFFOLK CONSTRUCTION |
| | TEL: 561-827-3678 |
| | E-MAIL: [email protected] |
| | : [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: THURS. NOV. 09/2017 |
| | ACTION: BUILDING PROVISO/ PARTIAL APPROVAL |
| | |
| | THIS SUBMITTAL IS FOR THE EXTERIOR GLAZING FLOORS 5-24. |
| | WITHIN THE CONTINENTAL GLAZING SYSTEMS CALCULATION AND |
| | PRODUCT APPROVAL BOOK (3) GLAZING SYSTEMS ARE |
| | IDENTIFIED, CONTINENTAL 2850 SERIES LIFT & SLIDING |
| | GLASS DOOR S. M. I (DATE 07/18/2017), 3900 SERIES |
| | WINDOW WALL SYSTEM (DATE 07/18/2017) & SERIES 3060 |
| | WINDOW WALL SYSTEMS (DATE 11/07/17). |
| | |
| | WITHIN THE SUBMITTED BOOKLET THE WINDOW SYSTEMS ARE |
| | IDENTIFIED STARTING WITH PAGE E01 & 01A (WINDOW WW-51 & |
| | 51A) THROUGH SHEET E38. WITHIN THE SUBMITTED PLANS THE |
| | E DRAWINGS START WITH E01 & 01A BUT STOP WITH E31A. THE |
| | PROJECT MANAGER FOR CONTINENTAL GLASS SYSTEMS CARLOS |
| | VARGAS TOLD US THAT E32-E38 ARE NOT INCLUDED IN THIS |
| | SUBMITTAL BUT WILL BE SUBMITTED UNDER SEPARATE COVER |
| | AND REVIEW FOR THE UPPER 25TH FLOOR. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| 2017-10-07 07:31:07 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17081172/ CONTINENTAL GLAZING |
| | SYSTEMS |
| | W. P. B. PERMIT: 15101020 |
| | ADD: 1100 S. FLAGLER DR. |
| | CONT: SUFFOLK CONST. |
| | TEL: 561-827-3678 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: FRI-SAT. OCT. 5-6TH./ 2017 |
| | ACTION: IN REVIEW/ SITE SPECIFIC PRODUCT APPROVAL TO BE |
| | REVIEWED BY THE BUILDING OFFICIAL ROBERT BROWN. |
| | |
| | 1) MULLIONS. IN THE FLORIDA PRODUCT APPROVAL REPORT FL. |
| | 18312.2 SERIES 3900 WINDOW WALL S. M. I. IN THE |
| | TECHNICAL SHEETS, SHEET 5 OF 11 INDICATES THE TYPE OF |
| | MULLIONS TESTED IN THIS REPORT. MULLION TYPES TESTED |
| | WERE M1, M1A, M2, M2A & J1 W/O REINFORCEMENT. |
| | |
| | IN REVIEWING MCY ENGINEERING SHEETS FOR SERIES 3900 |
| | WINDOW WALL SYSTEM ON PAGE 27 THE REPORT LIST THE |
| | VARIOUS MULLION TYPES FOR THIS SERIES: |
| | M1, TYPICAL MULLION +/-126.0 PSF |
| | J1, FX-SGD MULLION +/-104.9 PSF |
| | J3, FX-SGD MULLION +/-104.9PSF |
| | M2, TYPICAL MULLION (W/ STL REINFORCEMENT) +/-141.0 PSF |
| | M4, FX-SGD MULLION (W/ STL REINFORCEMENT) +/-138.8 PSF |
| | J1, FX-SGD MULLION (W/ STL REINFORCEMENT) +/-140.0 PSF |
| | |
| | ON PAGES 5 & 6 THERE ARE TABLES 2 & 3 SINGLE SPAN |
| | MULLION LOAD CAPACITY- PSF. THE CONCERNS ARE IN THE J1 |
| | COLUMN PORTION OF THE TABLES 2 & 3 THE J1 COLUMN. TO |
| | THE RIGHT OF THE SPAN TABLES ARE THE VARIOUS MULLION |
| | CONFIGURATIONS BOTH UNREINFORCED AND REINFORCED. THE |
| | VALUES OF PSF IN THE J1 COLUMN OF 141.0 WOULD SUGGEST |
| | THAT THE J1 MULLION SHOULD BE THE BOTTOM J1 LISTED |
| | ABOVE WITH STEEL REINFORCEMENT. THE TABLE 2 NOR 3 |
| | PROVIDE A DETAIL OF A J1 MULLION W/ STL REINFORCEMENT. |
| | |
| | IS THIS OF CONCERN SINCE IN REVIEWING ALL OF THE WIDOW |
| | CONFIGURATIONS IN THE 3900 SERIES CHARTS THERE IS NO J1 |
| | MULLIONS @ +/-104.9 NOR +/- 140.0? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED TO DETERMINE CODE COMPLIANCE |
| | WITH PRESSURES FOR COMPONENTS AND CLADDING. 2010 FBC-B |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |