Plan Review Notes
Plan Review Notes For Permit 17081172
Permit Number 17081172
Review Stop B
Sequence Number 2
Notes
Date Text
2017-11-09 11:11:562010 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17081172 WINDOW/ DOOR SUBMITTAL
 LEVELS 5-24
 W. P. B. PERMIT: 15111020 BUILDING PERMIT
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONSTRUCTION
 TEL: 561-827-3678
 E-MAIL: [email protected]
 : [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. NOV. 09/2017
 ACTION: BUILDING PROVISO/ PARTIAL APPROVAL
  
 THIS SUBMITTAL IS FOR THE EXTERIOR GLAZING FLOORS 5-24.
 WITHIN THE CONTINENTAL GLAZING SYSTEMS CALCULATION AND
 PRODUCT APPROVAL BOOK (3) GLAZING SYSTEMS ARE
 IDENTIFIED, CONTINENTAL 2850 SERIES LIFT & SLIDING
 GLASS DOOR S. M. I (DATE 07/18/2017), 3900 SERIES
 WINDOW WALL SYSTEM (DATE 07/18/2017) & SERIES 3060
 WINDOW WALL SYSTEMS (DATE 11/07/17).
  
 WITHIN THE SUBMITTED BOOKLET THE WINDOW SYSTEMS ARE
 IDENTIFIED STARTING WITH PAGE E01 & 01A (WINDOW WW-51 &
 51A) THROUGH SHEET E38. WITHIN THE SUBMITTED PLANS THE
 E DRAWINGS START WITH E01 & 01A BUT STOP WITH E31A. THE
 PROJECT MANAGER FOR CONTINENTAL GLASS SYSTEMS CARLOS
 VARGAS TOLD US THAT E32-E38 ARE NOT INCLUDED IN THIS
 SUBMITTAL BUT WILL BE SUBMITTED UNDER SEPARATE COVER
 AND REVIEW FOR THE UPPER 25TH FLOOR.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2017-10-07 07:31:072014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17081172/ CONTINENTAL GLAZING
 SYSTEMS
 W. P. B. PERMIT: 15101020
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONST.
 TEL: 561-827-3678
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: FRI-SAT. OCT. 5-6TH./ 2017
 ACTION: IN REVIEW/ SITE SPECIFIC PRODUCT APPROVAL TO BE
 REVIEWED BY THE BUILDING OFFICIAL ROBERT BROWN.
  
 1) MULLIONS. IN THE FLORIDA PRODUCT APPROVAL REPORT FL.
 18312.2 SERIES 3900 WINDOW WALL S. M. I. IN THE
 TECHNICAL SHEETS, SHEET 5 OF 11 INDICATES THE TYPE OF
 MULLIONS TESTED IN THIS REPORT. MULLION TYPES TESTED
 WERE M1, M1A, M2, M2A & J1 W/O REINFORCEMENT.
  
 IN REVIEWING MCY ENGINEERING SHEETS FOR SERIES 3900
 WINDOW WALL SYSTEM ON PAGE 27 THE REPORT LIST THE
 VARIOUS MULLION TYPES FOR THIS SERIES:
 M1, TYPICAL MULLION +/-126.0 PSF
 J1, FX-SGD MULLION +/-104.9 PSF
 J3, FX-SGD MULLION +/-104.9PSF
 M2, TYPICAL MULLION (W/ STL REINFORCEMENT) +/-141.0 PSF
 M4, FX-SGD MULLION (W/ STL REINFORCEMENT) +/-138.8 PSF
 J1, FX-SGD MULLION (W/ STL REINFORCEMENT) +/-140.0 PSF
  
 ON PAGES 5 & 6 THERE ARE TABLES 2 & 3 SINGLE SPAN
 MULLION LOAD CAPACITY- PSF. THE CONCERNS ARE IN THE J1
 COLUMN PORTION OF THE TABLES 2 & 3 THE J1 COLUMN. TO
 THE RIGHT OF THE SPAN TABLES ARE THE VARIOUS MULLION
 CONFIGURATIONS BOTH UNREINFORCED AND REINFORCED. THE
 VALUES OF PSF IN THE J1 COLUMN OF 141.0 WOULD SUGGEST
 THAT THE J1 MULLION SHOULD BE THE BOTTOM J1 LISTED
 ABOVE WITH STEEL REINFORCEMENT. THE TABLE 2 NOR 3
 PROVIDE A DETAIL OF A J1 MULLION W/ STL REINFORCEMENT.
  
 IS THIS OF CONCERN SINCE IN REVIEWING ALL OF THE WIDOW
 CONFIGURATIONS IN THE 3900 SERIES CHARTS THERE IS NO J1
 MULLIONS @ +/-104.9 NOR +/- 140.0? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED TO DETERMINE CODE COMPLIANCE
 WITH PRESSURES FOR COMPONENTS AND CLADDING. 2010 FBC-B
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  