| Plan Review Notes For Permit 17081130 |
| Permit Number |
17081130 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-29 11:54:54 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17081130 | | | 8/29/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHOW THE LOCATION OF THE AC CONDENSER ON THE PLAN | | | AND PROVIDE TIE-DOWN ENGINEERING- SECTION M1305.1.4.1 | | | AND M1401.4 FBC-14 RESIDENTIAL. | | | | | | 2) SOME OF THE TITLE BLOCK PRINT AT THE BOTTOM OF THE | | | AC PLAN IS ILLEGIBLE- PLEASE CORRECT- SECTION 107.2.1 | | | WPB AMENDMENTS TO THE FBC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|