Plan Review Notes
Plan Review Notes For Permit 17081108
Permit Number 17081108
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-30 08:02:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, SCOPE NOT CLEAR. NOTHING NEW IS CLOUDED AND
 THERE IS NO REVISION 2 INDICATED.
  
 2. IT APPEARS THAT A JOIST REPAIR DETAIL WAS ADDED, BUT
 NOTHING ON THE FLOOR PLAN INDICATES THE EXTENT OF THE
 PROPOSED REPAIR - SUCH AS, ONE JOIST OR THE ENTIRE
 FLOOR? LOCATION(S)? REVISE PLAN TO SHOW SCOPE.
  
 3. IF JOIST REPAIR IS REQUIRED, IT APPEARS THAT A VALUE
 WOULD BE ASSOCIATED WITH THE WORK. VALUE FOR REVISION
 ON THE REVISION FORM IS BLANK. FBC 109, PROVIDE VALUE
 FOR THE BUILDING, ELECTRICAL, PLUMBING REVISION.
  
 4. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS. OLD SHEETS SHOULD BE MARKED "VOID" AN BE INCLUDED
 IN THE SUBMITTAL BUT NOT BOUND WITH THE REVISION SETS.
  
  
  
  