| Plan Review Notes For Permit 17081093 |
| Permit Number |
17081093 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-15 07:49:47 | CHANGED STATUS TO FAILED, 2ND SERVICVE NOT PERMITTED | | | PER NEC 230.2 | | 2017-09-18 11:50:11 | CONDUIT FOR M.B. PANEL MUST BE RAN UNDERGROUND OR ITS A | | | VIOLATION OF NEC 230.70 (A) (1) | | | NEEDS SMOKE DETECTORS FBC 314 & 315 | | | BOND GAS LINE AND COLD WATER PIPE NEC 250.104 | | | | | | | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | DEVELOPMENT SERVICES DEPT. | | | CELL 561-657-1653 | | | [email protected] | | | |
|