Plan Review Notes
Plan Review Notes For Permit 17081077
Permit Number 17081077
Review Stop M
Sequence Number 1
Notes
Date Text
2017-10-04 15:58:16PLAN
 REVIEW COMMENTS
 (CONTRIBUTING HISTORIC STRUCTURES)
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) THE MECHANICAL PLANS ARE ARE NOT ACCEPTABLE. THE
 DUCTWORK AND EQUIPMENT CAN NOT BE SEEN CLEARLY DUE TO
 THE LAYERS WITH THE FURNITURE AND FIXTURES THAT ARE ON
 THE DRAWINGS. PLEASE SUBMIT MECHANICAL PLANS THAT
 CLEARLY SHOW THE MECHANICAL EQUIPMENT AND DUCT WORK. IN
 ADDITION TO THE REQUIRED MECHANICAL ITEMS, ONLY THE
 WALLS AND ROOM LABELS SHOULD BE SHOWN ON THE DRAWINGS.
 FBC 107.2.1
  
 3) THE SIZES OF ALL OF THE DUCTS ARE REQUIRED TO BE
 SHOWN ON THE DRAWINGS. FBC 107.3.5.1.4