| Plan Review Notes For Permit 17081077 |
| Permit Number |
17081077 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-04 15:58:16 | PLAN | | | REVIEW COMMENTS | | | (CONTRIBUTING HISTORIC STRUCTURES) | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | | | 2) THE MECHANICAL PLANS ARE ARE NOT ACCEPTABLE. THE | | | DUCTWORK AND EQUIPMENT CAN NOT BE SEEN CLEARLY DUE TO | | | THE LAYERS WITH THE FURNITURE AND FIXTURES THAT ARE ON | | | THE DRAWINGS. PLEASE SUBMIT MECHANICAL PLANS THAT | | | CLEARLY SHOW THE MECHANICAL EQUIPMENT AND DUCT WORK. IN | | | ADDITION TO THE REQUIRED MECHANICAL ITEMS, ONLY THE | | | WALLS AND ROOM LABELS SHOULD BE SHOWN ON THE DRAWINGS. | | | FBC 107.2.1 | | | | | | 3) THE SIZES OF ALL OF THE DUCTS ARE REQUIRED TO BE | | | SHOWN ON THE DRAWINGS. FBC 107.3.5.1.4 |
|