2017-09-18 16:14:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION INCLUDES 1 WATT PER SQUARE FOOT FOR
 UNCONDITIONED SPACE. PROVIDE CODE SECTION THAT PERMITS
 THIS. FBC 107.2.1
 2. LOAD CALCULATION SHOWS 4850 WATTS FOR WATER HEATER
 WITH CIRCULATING PUMP. PLAN SHOWS 2 TANKLESS WATER
 HEATERS, 1 EXISTING AND 1 ADDED. WHAT IS THE CORRECT
 AMOUNT OF LOAD FOR WATER HEATERS? ARE THERE TANKLESS
 AND STANDARD WATER HEATERS? PROVIDE CLARIFICATION
 AND/OR CORRECTION. FBC 107.2.1, NEC 220
 3. LOAD CALCULATION SHOWS 2 SMALL APPLIANCE CIRCUITS.
 THE PANEL SCHEDULE SHOWS THAT THERE ARE 3. PER NEC
 220.83, EACH SMALL APPLIANCE CIRCUIT IS REQUIRED TO BE
 INCLUDED IN CALCULATION. NEC 220.83; FBC RE 3602.3
 4. LOAD CALCULATION DOES NOT INCLUDE WINE COOLER. ALL
 NAMEPLATE RATINGS OF EQUIPMENT MUST BE INCLUDED IN
 CALCULATION. PROVIDE CORRECTION. NEC 220.83; FBC RE
 3602.3
 5. LOAD CALCULATION SHOWS "ALLOWANCE" FOR SEVERAL
 ITEMS. AN ALLOWANCE IS NOT ACCEPTABLE FOR THIS TYPE OF
 LOAD CALCULATION. ALL NAMEPLATE RATINGS OF EQUIPMENT
 MUST BE INCLUDED IN CALCULATION. PROVIDE CORRECTION.
 NEC 220.83; FBC RE 3602.3
 6. LOAD CALCULATION SHOWS 15.75 KW FOR A/C LOAD. PER
 THE SPECS ON MECHANICAL PLAN, THE 3 CONDENSING UNITS
 WOULD EQUAL 16.8 KW. PROVIDE DETAIL OF A/C VS HEAT LOAD
 IN CALCULATION, USING THE LARGEST OF THE LOADS. PROVIDE
 CORRECTION. FYI, IT APPEARS THAT WHEN ALL OF THE
 COMMENTS RELATING TO LOAD CALCULATION ARE CORRECTED,
 THE EXISTING SERVICE OF 200 AMPS WILL BE TOO SMALL.
 PROVIDE CORRECTION IF NECESSARY. NEC 220.83, 230.42;
 FBC RE 3602.3
 7. PROVIDE MORE DETAIL IN PANEL SCHEDULES. PROVIDE
 CIRCUIT IDENTIFICATION ("EXISTING CIRCUIT" NOT
 ACCEPTABLE), PROVIDE WIRE SIZE OF CIRCUIT, AND PROVIDE
 THE LOAD FOR EACH CIRCUIT. IF LOAD IS INCLUDED IN
 GENERAL LIGHTING PORTION, SO NOTE. INDICATE AFCI OR
 GFCI PROTECTION WHERE REQUIRED TO COMPLY WITH CODE.
 ALSO SHOW WHAT THE ACTUAL LOAD ON EACH PANEL IS, THE
 GARAGE PANEL AND MAIN PANEL DO NOT LIST THE AMOUNT OF
 LOAD ON PANEL. THE GARAGE PANEL IS FED FROM A 50 AMP
 CIRCUIT, IS THIS ADEQUATE FOR THE LOAD ON PANE? NEC
 210.8, 210.12, 215.2, 215.5, 408.4, 408.30; FBC
 RE3706.2, RE3902; FBC 107.2.1
 8. MASTER CLOSET SHOWS STANDARD 4 INCH RECESS LIGHTS.
 PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION.
 NEC 410.16; FBC RE4003.12
 9. MASTER BATH SHOWS A RECEPTACLE ADJACENT TO THE
 TOILET THAT DOES NOT HAVE GFCI PROTECTION. ALL
 RECEPTACLES IN THE BATHROOM REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.1
 10. PROVIDE RECEPTACLE AND LIGHT CONTROLLED BY A SWITCH
 AT EACH AHU IN ATTIC SPACE. FBC RE M1305.1.3.1
 11. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
 12. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
 13. LIGHTING ADJACENT TO POOL NOT CODE COMPLIANT.
 PROVIDE CORRECTION. NEC 680.22(B); FBC RE 4203.4
 14. RECEPTACLES FOR GDO REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE3902.2
 15. GUEST ROOM CLOSET LIGHT IS SHOWN AS A 4 INCH RECESS
 LIGHT. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. NEC 410.16; FBC RE4003.12
 16. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. PROVIDE CORRECTION. A NOTE WILL SUFFICE.
 NEC 210.12; FBC RE3902.12
 17. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 18. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  