| 2017-08-25 13:15:21 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE A DRAWING SHOWING THE LOCATION OF THE |
| | SHOWER DRAIN AND THE SLOPE OF THE FLOOR PITCHED TO THE |
| | SHOWER DRAIN. PER FBC PL 417.5.2 |
| | |
| | 2. PLEASE PROVIDE A DRAWING SHOWING THE LOCATION OF THE |
| | SHOWER VALVE AND MANUFACTURE SPEC. PER FBC PL 424.1/ |
| | 424.3 |
| | |
| | 3. A TEMPERATURE LIMITING DEVISE IS REQUIRED ON FREE |
| | STANDING TUB VALVE PLEASE PLACE NOTE ON PLAN. PER FBC |
| | PL 424.5 |
| | |
| | 4. PLEASE PROVIDE MANUFACTURE SPECS FOR FREE STANDING |
| | TUB. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. IF THE TUB DRAIN IS A SLIP JOINT IT SHALL COMPLY |
| | WITH FBC PL 405.8 SLIP JOINT CONNECTIONS. |
| | SLIP JOINTS SHALL BE MADE WITH AN APPROVED ELASTOMER |
| | GASKET AND SHALL ONLY BE INSTALLED ON THE TRAP OUTLET, |
| | TRAP INLET AND WITHIN THE TRAP SEAL. FIXTURES WITH |
| | CONCEALED SLIP-JOINT CONNECTIONS SHALL BE PROVIDED WITH |
| | AN ACCESS PANEL OR UTILITY SPACE NOT LESS THAN 12 |
| | INCHES (305 MM) IN ITS SMALLEST DIMENSION OR OTHER |
| | APPROVED ARRANGEMENT SO AS TO PROVIDE ACCESS TO THE |
| | SLIP JOINT CONNECTIONS FOR INSPECTION AND REPAIR. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |