| Plan Review Notes For Permit 17081061 |
| Permit Number |
17081061 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-18 14:07:44 | FAUCET IN MASTER VALVE SHALL HAVE A TEMPERED MIXING | | | VALVE. IF INTEGRAL PROVIDE SPECIFICATION OR LOCATION | | | WHERE IT WILL BE PLACED FBC P2724.1 | | | | | | SHOWER SHOWS A WEDI SYSTEM PLEASE PROVIDE MANUFACTURE | | | SPECIFICATIONS. PLEASE PROVIDE WHAT STANDARD OF TESTING | | | METHODS WAS USED FOR PRODUCT APPROVAL. FBC P2609.4 | | | | | | SHOWER SHOWS A STEAM GENERATOR PLEASE PROVIDE | | | MANUFACTURE SPECIFICATION. THE STEAM UNIT IS UNDER A | | | THE SHOWER SEAT. HOW IS THE STEAM ENTERING THE SHOWER? | | | PLEASE CLARIFY WHAT TYPE OF PROTECTION IS BEING USED | | | AND SHOW WHERE IT GOING IN THE SHOWER. FBC AMENDMENTS | | | 107.2.1 | | | | | | HAND HELD SHOWER MUST HAVE INTEGRAL VACUUM BREAKER FBC | | | P2902.4.2 | | | | | | LAVS SHOW WALL MOUNTED FAUCET TO FIXTURE AND REQUIRE | | | VALVES SERVING IT. PLEASE SHOW AND CLARIFY IF BEING | | | INSTALLED UNDER SINK. FBC P2903.9.3 | | | | | | LAY OUT ON PLAN NOT TO CODE, PLEASE PROVIDE AN | | | ISOMETRIC DIAGRAM. SHOWER EXCEEDS LENGTH ON TRAP AND | | | VENTING. DRAIN, WASTE AND VENT PIPE SIZING AND RISER | | | DIAGRAM FBC P3004, P3005 | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | 561-805-6720 | | | [email protected] | | | |
|