Plan Review Notes
Plan Review Notes For Permit 17081061
Permit Number 17081061
Review Stop E
Sequence Number 1
Notes
Date Text
2017-09-18 09:50:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MORE DETAIL REQUIRED FOR RELOCATION OF STEAM
 GENERATOR. IS THIS UNIT RATED TO BE INSTALLED IN A DAMP
 LOCATION? HOW IS THE POWER SUPPLIED TO THE UNIT, WITH
 CORD AND PLUG OR DIRECT CONNECTED (NO RECEPTACLE
 PERMITTED IN SHOWER)? IS THE BENCH THIS IS LOCATED
 UNDER COMPLETELY ENCLOSED SO THE STEAM UNIT WOULD NOT
 ACTUALLY BE IN THE SHOWER? WHERE IS THE REQUIRED
 DISCONNECT FOR THIS UNIT? PROVIDE RESPONSES AND SPEC
 SHEET FOR UNIT. NEC 110.3, 406.9(C), 424.12(B), 424.19
 2. PROVIDE FLOOR PLAN SHOWING SMOKE/CO ALARMS IN EACH
 LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  