| 2017-09-18 09:50:28 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. MORE DETAIL REQUIRED FOR RELOCATION OF STEAM |
| | GENERATOR. IS THIS UNIT RATED TO BE INSTALLED IN A DAMP |
| | LOCATION? HOW IS THE POWER SUPPLIED TO THE UNIT, WITH |
| | CORD AND PLUG OR DIRECT CONNECTED (NO RECEPTACLE |
| | PERMITTED IN SHOWER)? IS THE BENCH THIS IS LOCATED |
| | UNDER COMPLETELY ENCLOSED SO THE STEAM UNIT WOULD NOT |
| | ACTUALLY BE IN THE SHOWER? WHERE IS THE REQUIRED |
| | DISCONNECT FOR THIS UNIT? PROVIDE RESPONSES AND SPEC |
| | SHEET FOR UNIT. NEC 110.3, 406.9(C), 424.12(B), 424.19 |
| | 2. PROVIDE FLOOR PLAN SHOWING SMOKE/CO ALARMS IN EACH |
| | LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL EXISTING |
| | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |