| Notes |
| Date |
Text |
| 2017-09-06 17:15:50 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17081018 | | | 9/6/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | | HEAT PUMP SYSTEM- SECTION 312.1. | | | | | | 2) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR | | | THE O/A INTAKE DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 3) SHOW THE LOCATION OF THE NEW HEAT PUMP CONDENSER AND | | | PROVIDE ENGINEERED INSTALLATION DETAILS- SECTION | | | 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|