Plan Review Notes
Plan Review Notes For Permit 17081018
Permit Number 17081018
Review Stop M
Sequence Number 1
Notes
Date Text
2017-09-06 17:15:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17081018
 9/6/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 HEAT PUMP SYSTEM- SECTION 312.1.
  
 2) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR
 THE O/A INTAKE DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 3) SHOW THE LOCATION OF THE NEW HEAT PUMP CONDENSER AND
 PROVIDE ENGINEERED INSTALLATION DETAILS- SECTION
 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER