2017-08-31 12:56:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
 2. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS,
 HOODS, ETC. FBC 105.1
 3. PROVIDE LOAD CALCULATION FOR EXISTING BUSS TO
 CONFIRM ADEQUATE SIZE FOR ADDITIONAL LOAD. NEC 220; FBC
 107.2.1
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10
 6. PANEL SCHEDULE FOR PANEL H SHOWS CIRCUIT 13, 15, 17
 ON A 60 AMP BREAKER WITH # 6 WIRE TO TRANSFORMER. RISER
 DIAGRAM SHOWS # 8 WIRE TO TRANSFORMER. PROVIDE
 CORRECTION. NEC 215.2, 215.5, 310.15(B)(16); FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  