| 2017-08-24 06:59:49 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17081018 |
| | ADD: 500 S AUSTRALIAN AVE. SUITE:200 |
| | CONT: KARL CORP. CONSTRUCTION SERVICES |
| | TEL: 561-718-5569 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. AUGUST 24/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET INDICATES THIS NEW TENANT SPACE IS |
| | BEING SEPARATED OUT OF A LARGER TENANT SPACE. PLEASE |
| | PROVIDE THE REMAINING SQUARE FEET OF THE ORIGINAL |
| | TENANT SPACE. 2014 EXISTING BUILDING CODE LEVEL II |
| | 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | CREATION OR EXTENSION OF NONCONFORMITY. ALL NEW WORK, |
| | RE-CONFIGURATION SHALL NOT CREATE OR EXTEND ANY |
| | NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE |
| | RE-CONFIGURATION OF SPACE IS BEING MADE WITH REGARD TO |
| | ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE SAFETY, MEANS |
| | OF EGRESS, OR THE CAPACITY OF MECHANICAL, PLUMBING, OR |
| | ELECTRICAL SYSTEMS. |
| | 2) THE COVERSHEET INDICATES THE OCCUPANCY AS BUSINESS |
| | WITH 3115 SQ. FT. AND AN OCCUPANT LOAD OF ONLY 31. |
| | PLEASE NOTE WHEN IN REGARDS TO OCCUPANTS WHEN THERE IS |
| | A REMAINDER YOU ALWAYS ROUND UP OR 32 OCCUPANTS. 2014 |
| | FBC-B TABLE 1004.1.2 & THE BUILDING OFFICIALS |
| | ASSOCIATION OF FLORIDA, INFORMAL INTERPRETATION REPORT |
| | # 5479 IN CONJUNCTION WITH FL. DEPT. OF COMMUNITY |
| | AFFAIRS. |
| | |
| | 3) SHEET A-2.1 VERSES THE COVERSHEET/ LIFE SAFETY. THE |
| | COVERSHEET SHOWS THE NEW TENANT SEPARATION WALL AS A |
| | 1-HOUR FIRE RATED WALL WHEREAS SHEET A-2.1 INDICATES |
| | WALL TYPE # 4 A NON-RATED PARTITION TO THE UNDERSIDE OF |
| | THE PARTITION. SHEET A-3.1 DETAIL 04 ALSO SHOWS THIS |
| | TYPE WALL AS NON-BEARING, NON-RATED. 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED DISCREPANCY IN PLANS. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |