| Date |
Text |
| 2017-11-02 15:12:09 | FIRE REVIEW PASSED WITHOUTH FIRE PUMP, CHANGES |
| | ELECTRICAL STATUS TO PASS. 11-2-17 |
| 2017-10-26 14:12:29 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | PREVIOUS COMMENTS CORRECTED HAVE BEEN REMOVED AND NOTED |
| | AS CORRECTED. REMAINING PREVIOUS COMMENTS HAVE THE |
| | ORIGINAL COMMENT THAT STILL NEEDS CORRECTION WITH |
| | FURTHER COMMENT IN (PARENTHESES). |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23. |
| | IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF |
| | SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP |
| | SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM |
| | WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5, |
| | 695.4(B)(3); FBC 107.2.1 (JOCKEY PUMP AND ENTIRE FIRE |
| | PUMP SYSTEM HAS BEEN REMOVED FROM PLANS. THIS WILL NEED |
| | TO BE ON PLAN FOR THE FOUNDATION PERMIT BECAUSE THE |
| | WIRING TO THE FIRE PUMP NEEDS TO MEET THE CODE |
| | REQUIREMENTS OF NEC 695.6). |
| | 5. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS |
| | FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E) |
| | (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS. |
| | THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT |
| | BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE |
| | CODE REQUIREMENTS OF NEC 695.6). |
| | 6. CORRECTED. |
| | 7. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR |
| | FIRE PUMP. NEC 695.3(B) (ENTIRE FIRE PUMP SYSTEM HAS |
| | BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN |
| | FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE |
| | FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC |
| | 695.6 AND 695.14. SHOW LOCATION ON PLAN OF FIRE PUMP |
| | ROOM AND THE ELECTRICAL FEED TO THAT ROOM FROM PRIMARY |
| | AND SECONDARY SOURCE.) |
| | 8. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER |
| | AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING, |
| | AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6 |
| | (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS. |
| | THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT |
| | BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE |
| | CODE REQUIREMENTS OF NEC 695.6). |
| | 9. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE |
| | FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE |
| | 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS |
| | SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE |
| | 430.251(B); FBC 107.2.1 (ENTIRE FIRE PUMP SYSTEM HAS |
| | BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN |
| | FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE |
| | FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC |
| | 695.6). |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |