2017-09-06 17:02:151ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TRAP PRIMER VALVES ARE REQUIRED ON ALL FLOOR DRAINS
 TRAP GUARDS ARE NOT APPROVED. PER FBC PL 1002.4 TRAP
 SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
 2. THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PL
 708.3.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  