| 2017-09-06 17:02:15 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. TRAP PRIMER VALVES ARE REQUIRED ON ALL FLOOR DRAINS | | | TRAP GUARDS ARE NOT APPROVED. PER FBC PL 1002.4 TRAP | | | SEALS. | | | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS | | | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 | | | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO | | | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO | | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE | | | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A | | | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR | | | ASSE 1044. | | | | | | 2. THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE | | | BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PL | | | 708.3.5 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|