2017-10-25 08:29:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 PREVIOUS COMMENTS CORRECTED HAVE BEEN REMOVED AND NOTED
 AS CORRECTED. REMAINING PREVIOUS COMMENTS HAVE THE
 ORIGINAL COMMENT THAT STILL NEEDS CORRECTION WITH
 FURTHER COMMENT IN (PARENTHESES).
  
 1. CORRECTED.
 2. CORRECTED.
 3. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23.
 IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF
 SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP
 SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM
 WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5,
 695.4(B)(3); FBC 107.2.1 (JOCKEY PUMP AND ENTIRE FIRE
 PUMP SYSTEM HAS BEEN REMOVED FROM PLANS. THIS WILL NEED
 TO BE ON PLAN FOR THE FOUNDATION PERMIT BECAUSE THE
 WIRING TO THE FIRE PUMP NEEDS TO MEET THE CODE
 REQUIREMENTS OF NEC 695.6).
 4. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS
 FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E)
 (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS.
 THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT
 BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE
 CODE REQUIREMENTS OF NEC 695.6).
 5. CORRECTED.
 6. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR
 FIRE PUMP. NEC 695.3(B) (ENTIRE FIRE PUMP SYSTEM HAS
 BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN
 FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE
 FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC
 695.6 AND 695.14. SHOW LOCATION ON PLAN OF FIRE PUMP
 ROOM AND THE ELECTRICAL FEED TO THAT ROOM FROM PRIMARY
 AND SECONDARY SOURCE.)
 7. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER
 AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING,
 AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6
 (ENTIRE FIRE PUMP SYSTEM HAS BEEN REMOVED FROM PLANS.
 THIS WILL NEED TO BE ON PLAN FOR THE FOUNDATION PERMIT
 BECAUSE THE WIRING TO THE FIRE PUMP NEEDS TO MEET THE
 CODE REQUIREMENTS OF NEC 695.6).
 8. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE
 FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE
 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS
 SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE
 430.251(B); FBC 107.2.1 (ENTIRE FIRE PUMP SYSTEM HAS
 BEEN REMOVED FROM PLANS. THIS WILL NEED TO BE ON PLAN
 FOR THE FOUNDATION PERMIT BECAUSE THE WIRING TO THE
 FIRE PUMP NEEDS TO MEET THE CODE REQUIREMENTS OF NEC
 695.6).
  
 NEW COMMENT:
 9. ADDRESS ON THE PLANS SHOWS 2191 N AUSTRALIAN, PERMIT
 SHOWS 2181 N AUSTRALIAN. PROVIDE CORRECT ADDRESS ON
 PLANS. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER