Plan Review Notes
Plan Review Notes For Permit 17081012
Permit Number 17081012
Review Stop P
Sequence Number 2
Notes
Date Text
2017-10-25 11:51:421) A COMPLETE SET OF PLUMBING PLANS HAS BEEN SUBMITTED
 FOR REVIEW. THE PERMIT APPLICATION IS FOR A FOUNDATION
 ONLY PERMIT. SUBMIT PLUMBING PLANS THAT REFLECT THE
 SCOPE OF WORK TO BE INSTALLED FOR THE FOUNDATION PERMIT
 ONLY. THE PLANS ARE VAGUE AS TO WHAT IS BEING INSTALLED
 AT THIS TIME. WPB AMEND. TO FBC SEC. 107.2.1.
 2) PLACE A NOTE ON THE PLANS THAT THE PLUMBING RISERS
 FOR THE UNDERGROUND COLLECTION SYSTEMS ( SANITARY,
 STORM, WATER, COND., ETC.) WILL TERMINATE A MAXIMUM OF
 2 FEET ABOVE THE SLAB AND TERMINATE WITH AN APPROVED
 CAP OR PLUG.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW